Walkthrough: Burleigh Manor Middle School: July 16th, 2024 (WXBMMS202400053E)

Findings

Tracking Number Comments Location Assigned To Closed
FXBMMS2024002B44
Miscellaneous finding
Damaged paint on wall panels. Room 127 Building Services No
FXBMMS2024002B43
Obstruction(s) to airflow
The return vent is blocked. It is recommended… Room 127 Administration Yes
FXBMMS2024002B42
Missing escutcheon plate
Missing escutcheon plate. If not already being… Room 129 Custodial Services Yes
FXBMMS2024002B41
Plumbing fixture leaking/draining slowly
Hot water handle on faucet was leaking. Room 155 Building Services No
FXBMMS2024002B40
Appliances (toaster/coffee maker/fridge/space heaters/air cleaners other than HEPA)
A miniature refrigerator and a microwave were… Room 155 Administration Yes
FXBMMS2024002B3F
General Cleanliness/Dust
Dust observed underneath the sink. Custodial to… Room 130 Custodial Services Yes
FXBMMS2024002B3E
Miscellaneous finding
Missing lead signage. Room 167 Building Services No
FXBMMS2024002B3D
Non-issued disinfectants/aerosol sprays
A non-issued disinfectant spray was observed… Room 163 Administration Yes
FXBMMS2024002B3C
Appliances (toaster/coffee maker/fridge/space heaters/air cleaners other than HEPA)
A miniature refrigerator was observed. If not… Room 164 Administration Yes
FXBMMS2024002B3B
Wall-mounted unit requires cleaning/general preventative maintenance
Wall mounted unit was visibly dirty and require… Room 165 Building Services No
FXBMMS2024002B3A
Appliances (toaster/coffee maker/fridge/space heaters/air cleaners other than HEPA)
A miniature refrigerator and a microwave were… Room 141 Administration Yes
FXBMMS2024002B05
Miscellaneous finding
Missing lead signage. 133-A Building Services No
FXBMMS2024002B04
Plumbing fixture leaking/draining slowly
Sprinkler pump was observed to be leaking. Room 145 Building Services No
FXBMMS2024002B03
Holes/Penetrations in Wall
Rust was observed on the bottom of door frame.… Room 132 Building Services No
FXBMMS2024002B01
Signs of insects or evidence of pest
Ants near exterior door. If not already being… Room 132 Custodial Services Yes
FXBMMS2024002B00
Appliances (toaster/coffee maker/fridge/space heaters/air cleaners other than HEPA)
A miniature refrigerator and microwave were… Room 176 Administration Yes
FXBMMS2024002AFF
Air freshener/essential oils
Remind staff air fresheners, plug-ins, scent oil… 206 bath Administration Yes
FXBMMS2024002AFE
Appliances (toaster/coffee maker/fridge/space heaters/air cleaners other than HEPA)
A miniature refrigerator was observed. If not… Room 206 Administration Yes
FXBMMS2024002AFD
Appliances (toaster/coffee maker/fridge/space heaters/air cleaners other than HEPA)
Space heaters are not permitted per the Fire… Room 2013 Administration Yes
FXBMMS2024002AFC
Obstruction(s) to airflow
The return vent is blocked. It is recommended… Room 218 Administration Yes
FXBMMS2024002AFB
Appliances (toaster/coffee maker/fridge/space heaters/air cleaners other than HEPA)
A miniature refrigerator, coffee maker, and a… Room 218 Administration Yes
FXBMMS2024002AFA
General Cleanliness/Dust
Dead bugs observed in light fixture and require… Room 221 Custodial Services Yes
FXBMMS2024002AF9
Excess dirt or moisture or obstructed or purposely placed obstruction indicating occupant distress
The returns are visibly dirty and require dusting… Room 221 Custodial Services Yes
FXBMMS2024002AF7
Plumbing fixture leaking/draining slowly
Three leaking faucets at Station A, Station B,… Room 203 Building Services No
FXBMMS2024002AF6
Relative humidity above 70%
Relative humidity found to be at 71%. Room 216 Building Services No