Walkthrough: Centennial High School: January 23rd, 2023 (WXXCHS2023000431)

Findings

Tracking Number Comments Location Assigned To Closed Sort ascending
FXXCHS202300216B
Signs of insects or evidence of pest
Food readily accessible to insects and rodents.… Room 412 Administration Yes
FXXCHS202300215C
Stained/damaged tiles
Water stained ceiling tile(s). If not already… Portable 195 Custodial Services Yes
FXXCHS202300216C
Extension cords used as permanent wiring
The office has two tower fans hanging from the… Coaches office in men's locker room Administration Yes
FXXCHS202300215D
Tight seal on ceiling tiles
Center row of ceiling tiles not properly fitting… Portable 229 Building Services Yes
FXXCHS202300216D
General Cleanliness/Dust
The tops of the lockers had moderate dust… Team room in back of men's locker room Custodial Services Yes
FXXCHS202300215E
Uncomfortable temperature
The thermostat was reading 54 degrees (~@12pm). Portable 219 Building Services Yes
FXXCHS202300216E
Non-issued disinfectants/aerosol sprays
Scented aerosol air fresheners were observed.… Room 412 Administration Yes
FXXCHS202300215F
Uncomfortable temperature
Thermostat reading 73 degrees. Portable 195 Building Services Yes
FXXCHS202300216F
Miscellaneous finding
Mineral salts observed on lower cement blocks on… Cafeteria Building Services Yes
FXXCHS2023002160
Obstruction(s) to airflow
The air return within the wall is blocked by… Portable 195 Administration Yes
FXXCHS2023002170
Exterior doors not fully sealed (daylight)
Both doors have daylight showing under the door… Portable 195 Building Services Yes