Indoor Environmental Quality General Assessment of Bellows Spring Elementary School: February 1st, 2022 (GXBSES2022000081)

Assessor
Christopher Madden
Date

Air Distribution and Terminal System (Assess 2-3 Locations per HVAC Zone)

Ductwork (Supply and Return)
Check OK Comments
Condition
No odors, noise or vibration
No
6-A - Fan within Roof Top Unit (RTU-9) noisy/excessive vibration (WO #158267).
Clean, no obstructions
Yes
Free from signs of moisture/mold, insects or rodents?
Yes
No noticeable air leaks
Yes
Plenum
Check OK Comments
Ceiling Tiles
Tight seal on all tiles
No
Kindergarten Vestibule - Ceiling tile out of alignment.
No stained/damaged tiles indicating high RH or moisture problem
Yes
Supply Diffusers, Return Grilles, Exhaust Grilles
Check OK Comments
Condition
No odors or unusual sounds
Yes
Clean, no excess dirt or moisture
No
6A, 6B, 6H - Return grilles dusty/dirty.
No obstruction to air flow
Yes
No purposely placed obstruction indicating occupant distress
Yes
Location
No short circuiting between supply and return
Yes
Doors
Doors not tight or difficult to close indicating large pressure differential
Yes

Building

Envelope
Check OK Comments
Foundation
No moisture penetration or signs of mold?
Yes
Doors and Windows
Caulking and weather stripping in good condition
No
Exterior window caulk deteriorating (WO #222305).
Classrooms (Assess 2 to 3 per HVAC System Zone)
Check OK Comments
Condition
Room is free of dust and clutter
No
Kindergarten (73) - Fabric materials (the individual who brought the materials in should have a cleaning plan in place). Kindergarten (73), 2B, Project Room 6 - Appliances (microwaves and fridge). Administration to determine if needed for instruction. If not, the Office of the Environment recommends removal (energy conservation). 64 - Artificial plants (collects dust/allergens). Recommend removal.
No stained or damage ceiling tiles
Yes
No visible mold present (walls, cabinets, under sinks, behind posters)
Yes
Relative Humidity
Not above 70%
Yes
Mechanical/Boiler Rooms (Assess Each)
Check OK Comments
Condition
Clean
Yes
No unusual noise or odor
Yes
No mold growth on insulation
Yes
Traps contain water
Yes
Chemical Storage
Containers capped
Yes
No evidence of an active spill
Yes
Fan Coil Units/VAV Boxes
Check OK Comments
Condition
No odors, or unusual noise or vibration
Yes