School
Assessor
Jeffrey Klenk
Date
Air Distribution and Terminal System (Assess 2-3 Locations per HVAC Zone)
Check | OK | Comments |
---|---|---|
Condition | ||
No odors, noise or vibration
|
Yes
|
|
Clean, no obstructions
|
Yes
|
|
Free from signs of moisture/mold, insects or rodents?
|
Yes
|
|
No noticeable air leaks
|
Yes
|
Check | OK | Comments |
---|---|---|
Ceiling Tiles | ||
Tight seal on all tiles
|
Yes
|
|
No stained/damaged tiles indicating high RH or moisture problem
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
No odors or unusual sounds
|
No
|
Room D13 had an aroma resembling a rubber floor / new product. A source could not be identified. An observation, no action necessary.
Room D16 had a wicker basket on top of the supply diffuser of the ventilation unit located along the exterior. Besides partially obstructing air flow, during cooling, the basket material could become damp and form mold growth. School administration is to remind staff not to place items on top of the unit's air supply diffuser.
|
Clean, no excess dirt or moisture
|
No
|
The exposed side of the supply air diffusers have dust accumulation and/or dirt smears in room D24. School custodial staff is to clean diffusers not leaving any visible residue.
|
No obstruction to air flow
|
Yes
|
|
No purposely placed obstruction indicating occupant distress
|
Yes
|
|
Location | ||
No short circuiting between supply and return
|
Yes
|
|
Doors | ||
Doors not tight or difficult to close indicating large pressure differential
|
Yes
|
Building
Check | OK | Comments |
---|---|---|
Foundation | ||
No moisture penetration or signs of mold?
|
Yes
|
|
Doors and Windows | ||
Caulking and weather stripping in good condition
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
Room is free of dust and clutter
|
No
|
An air freshener aroma was detected in room B59. The air freshener was not observed. School administration is to remind staff air fresheners of any kind are not permitted and is to be removed if present. Air fresheners may mask an odor of concern or be an irritant to others.
Room D16 had a large stuffed bear on a file cabinet and several other stuffed animals along the windows. School administration is to determine if these are required for educational instruction and if not have them removed or ensure they are vacuumed periodically.
|
No stained or damage ceiling tiles
|
No
|
Water stained ceiling tiles were observed in rooms A71 and C18 (near VAV marking on ceiling grid). If not already being addressed, school custodial staff is to submit a work order for Building Services to evaluate, correct leak, and replace ceiling tile.
|
No visible mold present (walls, cabinets, under sinks, behind posters)
|
No
|
The window sill in portable 191 was discolored / stained (not mold growth) from a past water event (rained evening prior to inspection and no moisture detected). Work order 206722.
|
Relative Humidity | ||
Not above 70%
|
No
|
The dehumidifiers present in portables 190 and 191 were not turned on at the time of the inspection (inspector turned on at the time of the finding). The relative humidity in portable 190 was at 68% and portable 191 was 72%. The dehumidifiers have been temporarily provided to portable classrooms to prevent possible mold growth due to extended elevated interior relative humidity (70%+) from the ventilation unit's fan being set to "on" instead of "auto" as a COVID precaution (ensures constant introduction of outdoor air).
|
Check | OK | Comments |
---|---|---|
Condition | ||
Clean
|
Yes
|
|
No unusual noise or odor
|
No
|
The bathroom in room A94 had a sound of trickling water around the toilet. Work order 206723.
|
No mold growth on insulation
|
Yes
|
|
Traps contain water
|
Yes
|
|
Chemical Storage | ||
Containers capped
|
Yes
|
|
No evidence of an active spill
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
No odors, or unusual noise or vibration
|
No
|
A table lamp was present near the thermostat in room A71. School administration is to inform staff not to place items that can give a false sense of room temperature near a thermostat.
|