Air Distribution and Terminal System (Assess 2-3 Locations per HVAC Zone)
Check | OK | Comments |
---|---|---|
Condition | ||
No odors, noise or vibration
|
Yes
|
|
Clean, no obstructions
|
Yes
|
|
Free from signs of moisture/mold, insects or rodents?
|
Yes
|
|
No noticeable air leaks
|
Yes
|
Check | OK | Comments |
---|---|---|
Ceiling Tiles | ||
Tight seal on all tiles
|
Yes
|
|
No stained/damaged tiles indicating high RH or moisture problem
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
No odors or unusual sounds
|
Yes
|
|
Clean, no excess dirt or moisture
|
Yes
|
|
No obstruction to air flow
|
Yes
|
|
No purposely placed obstruction indicating occupant distress
|
Yes
|
|
Location | ||
No short circuiting between supply and return
|
No
|
Thermostats settings in question and/or no tamper resistant cover in portables 27, 145, 231, and 232. Work Order 201988.
|
Doors | ||
Doors not tight or difficult to close indicating large pressure differential
|
Yes
|
Building
Check | OK | Comments |
---|---|---|
Foundation | ||
No moisture penetration or signs of mold?
|
Yes
|
|
Doors and Windows | ||
Caulking and weather stripping in good condition
|
No
|
Casework along the exterior wall in rooms 103 and 205 was wet as determined with the use of a moisture meter. Work Orders 202264 and 202266. A cafeteria column (along exterior wall on right side) was determined to have a small section (1 SF) of wet drywall. Work Order 202265. These findings will be further investigated during winter break. Sources of the leaks are being addressed.
|
Check | OK | Comments |
---|---|---|
Condition | ||
Room is free of dust and clutter
|
Yes
|
|
No stained or damage ceiling tiles
|
No
|
Water stained ceiling tiles observed in stairwell near rooms 113 & 114, hall between gym locker rooms, 145 (above pencil sharpener, 111 (TV studio; around return air grille), 106 (near return grille), 002 (near exit door), 217 (near return grille), and hall between rooms 237 & 238. If not already in progress, school custodial staff to submit a work order to Building Services to evaluate, correct source, and replace ceiling tile.
Plaster above locker bank 4668-4694 across from room 208 is blistering and wet as determined by the use of a moisture meter. Work Order 202268.
|
No visible mold present (walls, cabinets, under sinks, behind posters)
|
No
|
Mold growth on surfaces in portables 27, 61, and 145. Board-approved restoration contractor cleaned and disinfected portable furnishings as a precaution and placed a dehumidifier for a few days. The mold growth occurred due to an incorrect thermostat setting.
|
Relative Humidity | ||
Not above 70%
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
Clean
|
Yes
|
|
No unusual noise or odor
|
Yes
|
|
No mold growth on insulation
|
Yes
|
|
Traps contain water
|
Yes
|
|
Chemical Storage | ||
Containers capped
|
Yes
|
|
No evidence of an active spill
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
No odors, or unusual noise or vibration
|
Yes
|