Air Distribution and Terminal System (Assess 2-3 Locations per HVAC Zone)
Check | OK | Comments |
---|---|---|
Condition | ||
No odors, noise or vibration
|
No
|
Gym - Exhaust fan rattling (WO #202489).
|
Clean, no obstructions
|
Yes
|
|
Free from signs of moisture/mold, insects or rodents?
|
Yes
|
|
No noticeable air leaks
|
Yes
|
Check | OK | Comments |
---|---|---|
Ceiling Tiles | ||
Tight seal on all tiles
|
Yes
|
|
No stained/damaged tiles indicating high RH or moisture problem
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
No odors or unusual sounds
|
Yes
|
|
Clean, no excess dirt or moisture
|
Yes
|
|
No obstruction to air flow
|
Yes
|
|
No purposely placed obstruction indicating occupant distress
|
Yes
|
|
Location | ||
No short circuiting between supply and return
|
Yes
|
|
Doors | ||
Doors not tight or difficult to close indicating large pressure differential
|
Yes
|
Building
Check | OK | Comments |
---|---|---|
Foundation | ||
No moisture penetration or signs of mold?
|
Yes
|
|
Doors and Windows | ||
Caulking and weather stripping in good condition
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
Room is free of dust and clutter
|
No
|
Room 30 - Excessive dust on teacher lab bench. Behind Media next to Elevator Mechanical Room (Fridge & Microwave) and Upstairs Science Prep (Coffee Maker) - Staff should remove personal appliances for energy management purposes.
|
No stained or damage ceiling tiles
|
No
|
Stained ceiling tiles were observed throughout the building. Many of these were due to condensation related to the unscheduled shut-off of the schools boiler. Building Maintenance was aware of this and investigating it during the time of the IEQ Assessment. The following areas were observed with stained tiles: Tech Classroom (Across from Custodial Office), 74, Cafeteria (towards Windows), Outside of 12, Gym Office, School Storage (Guidance), Outside of 6, 9, and 36. If these areas continue to become stained after the boilers are returned to service, custodial is to place a work order if one is not already in progress.
|
No visible mold present (walls, cabinets, under sinks, behind posters)
|
Yes
|
|
Relative Humidity | ||
Not above 70%
|
No
|
Gym (71%) - This is not out of the ordinary and no concerns at this time as the gym is not provided with air conditioning.
|
Check | OK | Comments |
---|---|---|
Condition | ||
Clean
|
Yes
|
|
No unusual noise or odor
|
Yes
|
|
No mold growth on insulation
|
Yes
|
|
Traps contain water
|
Yes
|
|
Chemical Storage | ||
Containers capped
|
Yes
|
|
No evidence of an active spill
|
No
|
Downstairs Staff Bathroom (across from 30) - Hot water handle leaking when on (WO #202492).
|
Check | OK | Comments |
---|---|---|
Condition | ||
No odors, or unusual noise or vibration
|
No
|
Room 6 - FCU Front Cover not attached to unit (WO #202489).
Room 3, 17, and Art - FCU partially blocked with stacked materials. Moved while onsite.
|