School
Assessor
Hummy Khan
Date
Outdoor Temperature
34°F
Relative Humidity
35%
Outdoor Dew Point
11°F
Air Handling Unit (Assess representative sample of RTU/AHU, including Portables)
Check | OK | Comments |
---|---|---|
Tag Number | ||
Displayed
|
Yes
|
|
Status | ||
Running
|
Yes
|
Check | OK | Comments |
---|---|---|
Outdoor Pollution | ||
Free from pollution sources w/i 25 ft. (e.g. dumpster, chimney, etc.)
|
Yes
|
|
Louvers and Access Doors | ||
Operating properly
|
Yes
|
|
Deflectors & Screens | ||
Present
|
Yes
|
|
No debris
|
Yes
|
|
Dampers | ||
Outside air damper: no obstructions
|
No
|
RTU-6A and RTU-3 - Outside air dampers closed. RTU-2 - Outside air dampers closed on one side but partially open on the other side.
|
Return air damper: no obstructions
|
Yes
|
Check | OK | Comments |
---|---|---|
Clean | ||
No excess dirt, not used for storage
|
Yes
|
|
Insulation | ||
Secure and Clean
|
Yes
|
|
P-Trap (if present) | ||
Charged with liquid
|
Yes
|
Check | OK | Comments |
---|---|---|
Filters | ||
Free of any bypassing
|
Yes
|
|
Correct size
|
Yes
|
|
Free from excessive loading, dampness or odor
|
Yes
|
|
Not collapsed/not fallen off
|
Yes
|
|
Present (not missing)
|
Yes
|
|
Date and initials written
|
Yes
|
|
Heating Coils | ||
Clean, no noticeable leaks, or obstructions
|
Yes
|
|
Cooling Coils | ||
Clean, no noticeable leaks, or obstructions
|
Yes
|
|
Access: Free of any obstructions in area that may affect access
|
Yes
|
|
Condensation: No excess condensation problems
|
Yes
|
|
Blowoff: Free of water from coil blowoff
|
Yes
|
|
Condensate Pan and Drain Line | ||
No visible bacterial or fungal growth
|
Yes
|
|
Clean, no residue, no standing water
|
Yes
|
|
No Overflow, leakage, blockage, or damage
|
Yes
|
|
Proper slope, drain line ok, drainage acceptable, discharge okay
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
Operational
|
No
|
RTU-3- Relief fan not working.
|
No unusual odors, noise, or vibration
|
No
|
EF - 32 making noise.
|
Check | OK | Comments |
---|---|---|
Heating Central Plant | ||
Boiler operational
|
Yes
|
Check | OK | Comments |
---|---|---|
Thermostat | ||
Thermostat setting acceptable
|
No
|
Portable #39, 41 (thermostat-1), #42 (thermostat-2), 70 deg occupied heating space temperature during unoccupied mode. Portable # 235- Heating set point 74 deg instead of 70 deg. Portable # 41-2-"Replace battery" message on thermostat screen display.
Portable 43 - (thermostats 1 and 2) set point 71 instead of 70 deg. Portable 43 - (thermostat 1) set point 71 instead of 70 deg.
|
Thermostat cover
|
No
|
Portable # 235 - No thermostat cover. Portable 41- A front cover was missing but found it laying on a table and reinstalled it and locked it while on site.
|
Fan Mode Correct
|
Yes
|
|
Space Temperature Acceptable
|
No
|
Portable # 41-(Thermostat-2) - Maintaining 73 deg space temperature even though the heating set point is 70 deg. Portable #43 (Thermostat-2) maintaining 77 deg space temperature.
|
Work Order Number(s)
181091
Issues found durring this assessment have been assigned to the above
work order(s).
Work Order: 181091