Assessor
Hummy Khan
Date
Outdoor Temperature
55°F
Relative Humidity
86%
Outdoor Dew Point
52°F
Air Handling Unit (Assess representative sample of RTU/AHU, including Portables)
Check | OK | Comments |
---|---|---|
Tag Number | ||
Displayed
|
No
|
Two rooftop units do not have tag number but other units do.
|
Status | ||
Running
|
No
|
RTU-12 - Not running. Exhaust Fan 12 - EF does not appear to be running.
|
Check | OK | Comments |
---|---|---|
Outdoor Pollution | ||
Free from pollution sources w/i 25 ft. (e.g. dumpster, chimney, etc.)
|
Yes
|
|
Louvers and Access Doors | ||
Operating properly
|
Yes
|
|
Deflectors & Screens | ||
Present
|
Yes
|
|
No debris
|
Yes
|
|
Dampers | ||
Outside air damper: no obstructions
|
No
|
RTU (no tag number) - Outdoor air damper 100% closed.
|
Return air damper: no obstructions
|
Yes
|
Check | OK | Comments |
---|---|---|
Clean | ||
No excess dirt, not used for storage
|
Yes
|
|
Insulation | ||
Secure and Clean
|
Yes
|
|
P-Trap (if present) | ||
Charged with liquid
|
Yes
|
Check | OK | Comments |
---|---|---|
Filters | ||
Free of any bypassing
|
No
|
Smaller RTU (no tag number) - Bypass around filters due to incorrect sizing.
|
Correct size
|
No
|
Smaller RTU (no tag number) - Incorrect size filters
|
Free from excessive loading, dampness or odor
|
Yes
|
|
Not collapsed/not fallen off
|
Yes
|
|
Present (not missing)
|
Yes
|
|
Date and initials written
|
Yes
|
|
Heating Coils | ||
Clean, no noticeable leaks, or obstructions
|
Yes
|
|
Cooling Coils | ||
Clean, no noticeable leaks, or obstructions
|
Yes
|
|
Access: Free of any obstructions in area that may affect access
|
Yes
|
|
Condensation: No excess condensation problems
|
Yes
|
|
Blowoff: Free of water from coil blowoff
|
Yes
|
|
Condensate Pan and Drain Line | ||
No visible bacterial or fungal growth
|
Yes
|
|
Clean, no residue, no standing water
|
Yes
|
|
No Overflow, leakage, blockage, or damage
|
Yes
|
|
Proper slope, drain line ok, drainage acceptable, discharge okay
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
Operational
|
Yes
|
|
No unusual odors, noise, or vibration
|
No
|
Exhaust Fan 8 and11 - Rattling.
|
Check | OK | Comments |
---|---|---|
Heating Central Plant | ||
Boiler operational
|
Yes
|
Check | OK | Comments |
---|---|---|
Thermostat | ||
Thermostat setting acceptable
|
No
|
Portable 90- One thermostat (#2) system in "Cool" mode. Should be in "Auto" mode. Date and time on the thermostat is incorrect. Second thermostat (#1) display shows "Change air filter". Portable 88, 149- System in "Cool" mode, should be in "Auto". Portable 197- Schedule is not correct. Portable 230- Display shows "Change air filter".
|
Thermostat cover
|
Yes
|
|
Fan Mode Correct
|
No
|
Portable 197- Fan in "On" position, should be in "Auto".
|
Space Temperature Acceptable
|
No
|
Portable 149- Inside temperature 57 deg. f.
|
Misc. Comments
Work Order: 170554
Work Order Number(s)
170554
Issues found durring this assessment have been assigned to the above
work order(s).