Indoor Environmental Quality HVAC Assessment of Mount Hebron High School: May 31st, 2023 (HXMHHS20230000E0)

Assessor
Hummy Khan
Date
Outdoor Temperature
54°F
Relative Humidity
76%
Outdoor Dew Point
47°F

Air Handling Unit (Assess representative sample of RTU/AHU, including Portables)

Unit
Check OK Comments
Tag Number
Displayed
Yes
Work Order Closed by Building Maintenance
No tag number on one air handling unit (AHU) that has a plumbing vent attached to the unit.
Status
Running
Yes
Outdoor Air Intake and Outdoor Air Dampers
Check OK Comments
Outdoor Pollution
Free from pollution sources w/i 25 ft. (e.g. dumpster, chimney, etc.)
Yes
Work Order Closed by Building Maintenance
Plumbing vent attached to an AHU (no tag number) and appears to be for the support is less than 10 feet from outside air intake of the unit.
Louvers and Access Doors
Operating properly
Yes
Deflectors & Screens
Present
Yes
No debris
Yes
Dampers
Outside air damper: no obstructions
Yes
Work Order Closed by Building Maintenance
AHU-2 - Outside air dampers (OADs) closed.
Return air damper: no obstructions
Yes
Mixing Plenum
Check OK Comments
Clean
No excess dirt, not used for storage
Yes
Insulation
Secure and Clean
Yes
P-Trap (if present)
Charged with liquid
Yes
Filters and Coils
Check OK Comments
Filters
Free of any bypassing
Yes
Work Order Closed by Building Maintenance
AHU-3, AHU-4, and AHU-11- Air bypass around pre-filters. AHU-3 - Air bypass at final filter.
Correct size
Yes
Free from excessive loading, dampness or odor
Yes
Work Order Closed by Building Maintenance
AHU-4, AHU-8 and RTU-2- Pre-filter replaced in August 2021, approaching two years. The unit(s) with two sets of filters, pre and final filters, the pre-filters should be replaced at least once a year and the final filters every two years.
Not collapsed/not fallen off
Yes
Present (not missing)
Yes
Work Order Closed by Building Maintenance
AHU-3- At least one final filter missing causing bypass.
Date and initials written
Yes
Work Order Closed by Building Maintenance
AHU-5 and AHU-7- No filters installation date or initials of the installing technician on the filters.
Heating Coils
Clean, no noticeable leaks, or obstructions
Yes
Cooling Coils
Clean, no noticeable leaks, or obstructions
Yes
Access: Free of any obstructions in area that may affect access
Yes
Condensation: No excess condensation problems
Yes
Blowoff: Free of water from coil blowoff
Yes
Condensate Pan and Drain Line
No visible bacterial or fungal growth
Yes
Clean, no residue, no standing water
Yes
No Overflow, leakage, blockage, or damage
Yes
Proper slope, drain line ok, drainage acceptable, discharge okay
Yes
Fans and Motors
Check OK Comments
Condition
Operational
Yes
No unusual odors, noise, or vibration
Yes
Work Order Closed by Building Maintenance
Exhaust fan (EF)- 31 - Vibrating.
Central Plant
Check OK Comments
Chilled Water Central Plant
Chiller operational
Yes
Cooling tower operational
Yes
Heating Central Plant
Boiler operational
Yes
Portable(s)
Check OK Comments
Thermostat
Thermostat setting acceptable
Yes
Work Order Closed by Building Maintenance
Portable # 61 - Change air filter alarm. Portable # 145 - Thermostat in over-ride mode.
Thermostat cover
Yes
Fan Mode Correct
Yes
Space Temperature Acceptable
Yes
Work Order Number(s)
285637
Issues found durring this assessment have been assigned to the above work order(s).