Finding: Wilde Lake High School: multiple, see attached, other forms coming: 318, 300, 303, 302, (FXWLHS20180000C1)

Finding Type
Miscellaneous finding
Remediation

Work order 86612:  Building Services HVAC Shop repaired a broken linkage in air handling unit 6.  The damper controls in units 6 and 7 were adjusted and calibrated.  Completed work on September 21, 2018.

Work order 87523:  Building Services reviewed variable air volume boxes in rooms 320 and 324.  The motors were found to be bad and replaced.  The linkages were checked and re-connected as necessary.

Prior to this investigation, Building Services reviewed and addressed ventilation controls disrupted by roofing and fireproofing work which likely hindered thermal comfort.

 

Location
multiple, see attached, other forms coming: 318, 300, 303, 302,
Tracking Number
FXWLHS20180000C1
Assigned To
Building Services
Closed
Yes
Completion Date