Finding Type
Obstruction(s) to airflow
Comments
HVAC Shop to review how outdoor air is being introduced via existing ventilation serving the classroom. The past kindergarten addition reconfigured the ventilation in room 46. Based solely on a general visual below the drop ceiling, the existing unit ventilator no longer provides outdoor air (hallway was constructed where there was once an outdoor air intake grille) and observed what appears to be only perforated passive air return grates within drop ceiling.
Location
Room 46
Tracking Number
FSJLES20220020F6
Assigned To
Building Services
Work Orders
#266127
(Complete)
Closed
Yes
Completion Date