Assessor
Hummy Khan
Date
Outdoor Temperature
46°F
Relative Humidity
79%
Outdoor Dew Point
40°F
Air Handling Unit (Assess representative sample of RTU/AHU, including Portables)
Check | OK | Comments |
---|---|---|
Tag Number | ||
Displayed
|
Yes
|
|
Status | ||
Running
|
Yes
|
Check | OK | Comments |
---|---|---|
Outdoor Pollution | ||
Free from pollution sources w/i 25 ft. (e.g. dumpster, chimney, etc.)
|
Yes
|
|
Louvers and Access Doors | ||
Operating properly
|
Yes
|
|
Deflectors & Screens | ||
Present
|
Yes
|
|
No debris
|
Yes
|
|
Dampers | ||
Outside air damper: no obstructions
|
Yes Work Order Closed by Building Maintenance
|
Inconsistency on the position of the Outside Air Dampers (OADs) from one unit to the other. On some units, the OADs appear to be 100% open and on others, partially open. For example, RTU-1, the OADs are 100% open, while on RAHU-B, the OADs are partially open comparatively.
RAHU-A, ACU-1 and ACU-3 - OADs closed.
|
Return air damper: no obstructions
|
Yes
|
Check | OK | Comments |
---|---|---|
Clean | ||
No excess dirt, not used for storage
|
Yes
|
|
Insulation | ||
Secure and Clean
|
Yes
|
|
P-Trap (if present) | ||
Charged with liquid
|
Yes
|
Check | OK | Comments |
---|---|---|
Filters | ||
Free of any bypassing
|
Yes
|
|
Correct size
|
Yes
|
|
Free from excessive loading, dampness or odor
|
Yes
|
|
Not collapsed/not fallen off
|
Yes
|
|
Present (not missing)
|
Yes
|
|
Date and initials written
|
Yes Work Order Closed by Building Maintenance
|
ACU-1 and ACU-3- Filters dated June 2021, almost two years old. It appears that they were checked in February 2022 but were never replaced. These units have a single set (no pre-filter) of filters and should be replaced at least once a year.
|
Heating Coils | ||
Clean, no noticeable leaks, or obstructions
|
Yes
|
|
Cooling Coils | ||
Clean, no noticeable leaks, or obstructions
|
Yes
|
|
Access: Free of any obstructions in area that may affect access
|
Yes
|
|
Condensation: No excess condensation problems
|
Yes
|
|
Blowoff: Free of water from coil blowoff
|
Yes
|
|
Condensate Pan and Drain Line | ||
No visible bacterial or fungal growth
|
Yes
|
|
Clean, no residue, no standing water
|
Yes
|
|
No Overflow, leakage, blockage, or damage
|
Yes
|
|
Proper slope, drain line ok, drainage acceptable, discharge okay
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
Operational
|
Yes
|
|
No unusual odors, noise, or vibration
|
Yes Work Order Closed by Building Maintenance
|
Exhaust Fan-5 - Rattling.
|
Check | OK | Comments |
---|---|---|
Chilled Water Central Plant | ||
Chiller operational
|
Yes
|
Not running probably because the weather is still cold.
|
Cooling tower operational
|
Yes
|
Not running probably because the weather is still cold.
|
Heating Central Plant | ||
Boiler operational
|
Yes
|
Check | OK | Comments |
---|---|---|
Thermostat | ||
Thermostat setting acceptable
|
Yes Work Order Closed by Building Maintenance
|
Portable # 207, 252, and 253-Thermostat set on permanent hold, instead of running per schedule. Changed it to run on schedule while on site.
Portable # 207- "Change air filter" is displayed.
|
Thermostat cover
|
Yes
|
|
Fan Mode Correct
|
Yes Work Order Closed by Building Maintenance
|
Portable # 214- Fan was in "On" mode, instead of "Auto". Changed it to "Auto" while on site.
|
Space Temperature Acceptable
|
Yes
|
Misc. Comments
RAHU-B- The control panel door was open and the controls were exposed to the outdoor weather. Closed the door while on site but it won't latch properly. It is recommended Building Maintenance repair the door latch/lock.
Work Order Number(s)
282454
Issues found durring this assessment have been assigned to the above
work order(s).