School
Assessor
Jeffrey Klenk
Date
Air Distribution and Terminal System (Assess 2-3 Locations per HVAC Zone)
Check | OK | Comments |
---|---|---|
Condition | ||
No odors, noise or vibration
|
No
|
A paint like odor was detected in room 111. The room appears to have a new wood furniture toy set. No further action required.
|
Clean, no obstructions
|
Yes
|
|
Free from signs of moisture/mold, insects or rodents?
|
Yes
|
|
No noticeable air leaks
|
Yes
|
Check | OK | Comments |
---|---|---|
Ceiling Tiles | ||
Tight seal on all tiles
|
Yes
|
|
No stained/damaged tiles indicating high RH or moisture problem
|
No
|
Water stained ceiling tiles observed in hallway outside the first grade pod entrance (near a storage closet). Custodial staff is to submit a work order if not already submitted.
|
Check | OK | Comments |
---|---|---|
Condition | ||
No odors or unusual sounds
|
Yes
|
|
Clean, no excess dirt or moisture
|
No
|
The back side of air supply diffusers were dirty and are to be cleaned by detaching / opening to gain better access to the back of the fins. This was observed in rooms 5, 10, 16, 36, 64,71, 79 (media), and 92. It is assumed other rooms within the pod are the same and are to be reviewed and addressed by the school custodial staff.
|
No obstruction to air flow
|
No
|
Portable 159 thermostat LCD display is blank (Work Order 160321).
|
No purposely placed obstruction indicating occupant distress
|
Yes
|
|
Location | ||
No short circuiting between supply and return
|
Yes
|
|
Doors | ||
Doors not tight or difficult to close indicating large pressure differential
|
Yes
|
Building
Check | OK | Comments |
---|---|---|
Foundation | ||
No moisture penetration or signs of mold?
|
No
|
Room 92 has large voids in and spacing around conduit through the exterior block wall located above the drop ceiling (Work Order 160313).
Portable 110 has a small hole in metal siding near ramp door (left side of door). An overhang protects the void from inadvertent water entry (Work Order 160313).
Portable 159 has a significant tripping hazard where the wood boardwalk and metal ramp meet (Work Order 160313).
|
Doors and Windows | ||
Caulking and weather stripping in good condition
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
Room is free of dust and clutter
|
Yes
|
|
No stained or damage ceiling tiles
|
Yes
|
|
No visible mold present (walls, cabinets, under sinks, behind posters)
|
Yes
|
|
Relative Humidity | ||
Not above 70%
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
Clean
|
Yes
|
|
No unusual noise or odor
|
Yes
|
|
No mold growth on insulation
|
Yes
|
|
Traps contain water
|
Yes
|
|
Chemical Storage | ||
Containers capped
|
Yes
|
|
No evidence of an active spill
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
No odors, or unusual noise or vibration
|
Yes
|