School
Assessor
Jeffrey Klenk
Date
Air Distribution and Terminal System (Assess 2-3 Locations per HVAC Zone)
Check | OK | Comments |
---|---|---|
Condition | ||
No odors, noise or vibration
|
Yes
|
|
Clean, no obstructions
|
Yes
|
|
Free from signs of moisture/mold, insects or rodents?
|
Yes
|
|
No noticeable air leaks
|
Yes
|
Check | OK | Comments |
---|---|---|
Ceiling Tiles | ||
Tight seal on all tiles
|
Yes
|
|
No stained/damaged tiles indicating high RH or moisture problem
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
No odors or unusual sounds
|
Yes
|
|
Clean, no excess dirt or moisture
|
Yes Work Order Closed by Building Maintenance
|
The supply diffuser and exhaust grille (storage closet) within the school store/office (area 106) had visible dust accumulation. School custodial staff is to clean visible dust and any residual streaking.
|
No obstruction to air flow
|
Yes Work Order Closed by Building Maintenance
|
The turning vanes of the air returns at the right front corner (as you walk in) of the cafeteria appear to be obstructed with dust accumulation. Work order 250172.
|
No purposely placed obstruction indicating occupant distress
|
Yes
|
|
Location | ||
No short circuiting between supply and return
|
Yes
|
|
Doors | ||
Doors not tight or difficult to close indicating large pressure differential
|
Yes
|
Building
Check | OK | Comments |
---|---|---|
Foundation | ||
No moisture penetration or signs of mold?
|
Yes
|
|
Doors and Windows | ||
Caulking and weather stripping in good condition
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
Room is free of dust and clutter
|
Yes Work Order Closed by Building Maintenance
|
The tops of the hallway lockers in the music wing have moderate dust accumulation. School custodial staff is to clean the tops of the lockers (may have not received summer cleaning at the time of inspection).
|
No stained or damage ceiling tiles
|
Yes Work Order Closed by Building Maintenance
|
Water stained ceiling tiles observed in hallways (between restrooms outside drama office; stage bay door) and rooms 127, 171 (high ceiling), 310, 322, 327, and 338. If not already being addressed, school custodial staff is to submit a work order to Building Maintenance to assess and correct the leak then replace ceiling tile.
|
No visible mold present (walls, cabinets, under sinks, behind posters)
|
Yes
|
|
Relative Humidity | ||
Not above 70%
|
Yes Work Order Closed by Building Maintenance
|
The auditorium, cafeteria, and school store/office (106) had relative humidity over 70%. Work order 248150.
|
Check | OK | Comments |
---|---|---|
Condition | ||
Clean
|
Yes
|
|
No unusual noise or odor
|
Yes
|
|
No mold growth on insulation
|
Yes
|
|
Traps contain water
|
Yes
|
|
Chemical Storage | ||
Containers capped
|
Yes
|
|
No evidence of an active spill
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
No odors, or unusual noise or vibration
|
Yes
|
Work Order Number(s)
248150,250172
Issues found durring this assessment have been assigned to the above
work order(s).