Indoor Environmental Quality General Assessment of Centennial Lane Elementary School: August 26th, 2020 (GXCLES202000001A)

Assessor
Jeffrey Klenk
Date

Air Distribution and Terminal System (Assess 2-3 Locations per HVAC Zone)

Ductwork (Supply and Return)
Check OK Comments
Condition
No odors, noise or vibration
No
Ventilation units were to operate during regular school hours. Not all rooms or ventilation zones appeared to be operating based on no air flow from supply air diffusers and elevated interior room temperatures (81 degrees). Rooms included, but not limited to 111, 119, 130, 145, and 209. Work Order 165304.
Clean, no obstructions
Yes
Free from signs of moisture/mold, insects or rodents?
Yes
No noticeable air leaks
Yes
Plenum
Check OK Comments
Ceiling Tiles
Tight seal on all tiles
Yes
No stained/damaged tiles indicating high RH or moisture problem
Yes
Supply Diffusers, Return Grilles, Exhaust Grilles
Check OK Comments
Condition
No odors or unusual sounds
Yes
Clean, no excess dirt or moisture
Yes
No obstruction to air flow
Yes
No purposely placed obstruction indicating occupant distress
Yes
Location
No short circuiting between supply and return
Yes
Doors
Doors not tight or difficult to close indicating large pressure differential
Yes

Building

Envelope
Check OK Comments
Foundation
No moisture penetration or signs of mold?
No
Portable 88 had a safety concern regarding the walking surface. A void or sink hole formed in macadam pathway where it joins the wood ramp/boardwalk. Work Order 165305.
Doors and Windows
Caulking and weather stripping in good condition
No
Daylight shining through doors and/or weather strips failing or missing. Portable 88 (right side of ramp door), portable 90 (bottom and bottom right of ramp door), and portable 197 (ramp door). Work Order 165306. Questionable drywall moisture readings in portables 88 (bottom right of the ramp door) and 197 (bottom right of the window across from ramp door near closet). Work Order 165307.
Classrooms (Assess 2 to 3 per HVAC System Zone)
Check OK Comments
Condition
Room is free of dust and clutter
Yes
No stained or damage ceiling tiles
No
Portable 149 had a dry water stain on the drywall ceiling. Work Order 165307. Water stained ceiling tile in storage room 108 within health suite. School custodial staff is to submit a work order to Building Services unless already being addressed.
No visible mold present (walls, cabinets, under sinks, behind posters)
Yes
Relative Humidity
Not above 70%
Yes
Mechanical/Boiler Rooms (Assess Each)
Check OK Comments
Condition
Clean
Yes
No unusual noise or odor
Yes
No mold growth on insulation
Yes
Traps contain water
Yes
Chemical Storage
Containers capped
Yes
No evidence of an active spill
Yes
Fan Coil Units/VAV Boxes
Check OK Comments
Condition
No odors, or unusual noise or vibration
Yes