Assessor
Jeffrey Klenk
Date
Air Distribution and Terminal System (Assess 2-3 Locations per HVAC Zone)
Check | OK | Comments |
---|---|---|
Condition | ||
No odors, noise or vibration
|
Yes
|
|
Clean, no obstructions
|
Yes
|
|
Free from signs of moisture/mold, insects or rodents?
|
No
|
The HVAC wall unit in the computer lab located off the media center (room 110) had grime on the linear diffusers. Work order 182904.
|
No noticeable air leaks
|
Yes
|
Check | OK | Comments |
---|---|---|
Ceiling Tiles | ||
Tight seal on all tiles
|
Yes
|
|
No stained/damaged tiles indicating high RH or moisture problem
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
No odors or unusual sounds
|
Yes
|
|
Clean, no excess dirt or moisture
|
Yes
|
|
No obstruction to air flow
|
Yes
|
|
No purposely placed obstruction indicating occupant distress
|
Yes
|
|
Location | ||
No short circuiting between supply and return
|
Yes
|
|
Doors | ||
Doors not tight or difficult to close indicating large pressure differential
|
No
|
The interior side of the main door of portable 171 had a linear perforation towards the bottom of the door. Work order 182895.
|
Building
Check | OK | Comments |
---|---|---|
Foundation | ||
No moisture penetration or signs of mold?
|
Yes
|
|
Doors and Windows | ||
Caulking and weather stripping in good condition
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
Room is free of dust and clutter
|
No
|
Strong air freshener aroma in portable 252. An air freshener device was observed on a file cabinet. School administration is to remind staff member such devices are not permitted and is to be removed.
|
No stained or damage ceiling tiles
|
No
|
Water stained ceiling tiles observed in room 62 (in recessed closet / locker area) and commons of pod containing rooms 80-85 (near counter with sink). Custodial staff is to submit a work order to Building Services if not already being addressed.
|
No visible mold present (walls, cabinets, under sinks, behind posters)
|
Yes
|
|
Relative Humidity | ||
Not above 70%
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
Clean
|
Yes
|
|
No unusual noise or odor
|
Yes
|
|
No mold growth on insulation
|
Yes
|
|
Traps contain water
|
Yes
|
|
Chemical Storage | ||
Containers capped
|
Yes
|
|
No evidence of an active spill
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
No odors, or unusual noise or vibration
|
No
|
Chilled water fountain in commons of pod containing rooms 80-85 was rattling when the compressor came on. Loud nuisance noise and potential failure concern. Work order 182903.
Portable 252 thermostat did not have a tamper proof cover and had the wrong time of day. Work order 182898.
Portable 253 felt very cold. Thermostat did not have a tamper proof cover and LCD displayed LO and wrong time of day. Work order 182898.
Portable 171 thermostat did not have a tamper proof cover. Work order 182898.
Portable 164 HVAC unit was making a pulsing sound instead of an even / steady sound. Work order 182901.
|