Indoor Environmental Quality General Assessment of St. John’s Lane Elementary School: March 3rd, 2021 (GSJLES2021000036)

Assessor
Jeffrey Klenk
Date

Air Distribution and Terminal System (Assess 2-3 Locations per HVAC Zone)

Ductwork (Supply and Return)
Check OK Comments
Condition
No odors, noise or vibration
Yes
Clean, no obstructions
Yes
Free from signs of moisture/mold, insects or rodents?
No
The HVAC wall unit in the computer lab located off the media center (room 110) had grime on the linear diffusers. Work order 182904.
No noticeable air leaks
Yes
Plenum
Check OK Comments
Ceiling Tiles
Tight seal on all tiles
Yes
No stained/damaged tiles indicating high RH or moisture problem
Yes
Supply Diffusers, Return Grilles, Exhaust Grilles
Check OK Comments
Condition
No odors or unusual sounds
Yes
Clean, no excess dirt or moisture
Yes
No obstruction to air flow
Yes
No purposely placed obstruction indicating occupant distress
Yes
Location
No short circuiting between supply and return
Yes
Doors
Doors not tight or difficult to close indicating large pressure differential
No
The interior side of the main door of portable 171 had a linear perforation towards the bottom of the door. Work order 182895.

Building

Envelope
Check OK Comments
Foundation
No moisture penetration or signs of mold?
Yes
Doors and Windows
Caulking and weather stripping in good condition
Yes
Classrooms (Assess 2 to 3 per HVAC System Zone)
Check OK Comments
Condition
Room is free of dust and clutter
No
Strong air freshener aroma in portable 252. An air freshener device was observed on a file cabinet. School administration is to remind staff member such devices are not permitted and is to be removed.
No stained or damage ceiling tiles
No
Water stained ceiling tiles observed in room 62 (in recessed closet / locker area) and commons of pod containing rooms 80-85 (near counter with sink). Custodial staff is to submit a work order to Building Services if not already being addressed.
No visible mold present (walls, cabinets, under sinks, behind posters)
Yes
Relative Humidity
Not above 70%
Yes
Mechanical/Boiler Rooms (Assess Each)
Check OK Comments
Condition
Clean
Yes
No unusual noise or odor
Yes
No mold growth on insulation
Yes
Traps contain water
Yes
Chemical Storage
Containers capped
Yes
No evidence of an active spill
Yes
Fan Coil Units/VAV Boxes
Check OK Comments
Condition
No odors, or unusual noise or vibration
No
Chilled water fountain in commons of pod containing rooms 80-85 was rattling when the compressor came on. Loud nuisance noise and potential failure concern. Work order 182903. Portable 252 thermostat did not have a tamper proof cover and had the wrong time of day. Work order 182898. Portable 253 felt very cold. Thermostat did not have a tamper proof cover and LCD displayed LO and wrong time of day. Work order 182898. Portable 171 thermostat did not have a tamper proof cover. Work order 182898. Portable 164 HVAC unit was making a pulsing sound instead of an even / steady sound. Work order 182901.