School
Assessor
Hummy Khan
Date
Outdoor Temperature
46°F
Relative Humidity
59%
Outdoor Dew Point
36°F
Air Handling Unit (Assess representative sample of RTU/AHU, including Portables)
Check | OK | Comments |
---|---|---|
Tag Number | ||
Displayed
|
Yes Work Order Closed by Building Maintenance
|
No tag numbers on a few rooftop units (RTU), one large McQuay RTU located above the Auditorium and another McQuay unit next to Air Handling Unit (AHU-11) in the front of the building near the main entrance.
|
Status | ||
Running
|
Yes Work Order Closed by Building Maintenance
|
AHU-11 (Cafeteria) and AHU-(no tag number next to AHU-11) - Not running.
|
Check | OK | Comments |
---|---|---|
Outdoor Pollution | ||
Free from pollution sources w/i 25 ft. (e.g. dumpster, chimney, etc.)
|
Yes
|
|
Louvers and Access Doors | ||
Operating properly
|
Yes
|
|
Deflectors & Screens | ||
Present
|
Yes
|
|
No debris
|
Yes
|
|
Dampers | ||
Outside air damper: no obstructions
|
Yes Work Order Closed by Building Maintenance
|
Inconsistency on the position of the outside air dampers (OADs) from one unit to the other. On some units, the OADs appear to be 100% open and on others 100% closed while on others partially open. For example: Venmar units OSA-2 and McQuay Unit #6 - OADs are 100% open. OSA-1, OSA-3, RTU-4 (York) and HRU-7 - OADs100% closed.
AHU-(no tag number located next to AHU-11) not running but the OADs 100% open. This could cause coil to freeze up.
|
Return air damper: no obstructions
|
Yes
|
Check | OK | Comments |
---|---|---|
Clean | ||
No excess dirt, not used for storage
|
Yes
|
|
Insulation | ||
Secure and Clean
|
Yes
|
|
P-Trap (if present) | ||
Charged with liquid
|
Yes
|
Check | OK | Comments |
---|---|---|
Filters | ||
Free of any bypassing
|
Yes Work Order Closed by Building Maintenance
|
RTU-5 - Air bypass around filter.
|
Correct size
|
Yes
|
|
Free from excessive loading, dampness or odor
|
Yes Work Order Closed by Building Maintenance
|
HRU-7 and similar units in that area - Filters dated August 2021 (15 months old). Per the HCPSS filters replacement standard these filters should be replaced at least twice a year.
|
Not collapsed/not fallen off
|
Yes Work Order Closed by Building Maintenance
|
AHU-1-Munters/Deschamp unit) - Filters falling off.
|
Present (not missing)
|
Yes
|
|
Date and initials written
|
Yes Work Order Closed by Building Maintenance
|
No initials of the installing technicians on any filters.
|
Heating Coils | ||
Clean, no noticeable leaks, or obstructions
|
Yes
|
|
Cooling Coils | ||
Clean, no noticeable leaks, or obstructions
|
Yes
|
|
Access: Free of any obstructions in area that may affect access
|
Yes
|
|
Condensation: No excess condensation problems
|
Yes
|
|
Blowoff: Free of water from coil blowoff
|
Yes
|
|
Condensate Pan and Drain Line | ||
No visible bacterial or fungal growth
|
Yes
|
|
Clean, no residue, no standing water
|
Yes
|
|
No Overflow, leakage, blockage, or damage
|
Yes
|
|
Proper slope, drain line ok, drainage acceptable, discharge okay
|
Yes Work Order Closed by Building Maintenance
|
RTU-1, RTU-2, and RTU-6) and another RTU (no tag number, located above Auditorium) and several other units - Condensate drain improperly terminated, repeat finding.
|
Check | OK | Comments |
---|---|---|
Condition | ||
Operational
|
Yes
|
|
No unusual odors, noise, or vibration
|
Yes Work Order Closed by Building Maintenance
|
Exhaust fan (EF-4) rattling. Another EF (no tag number-on same roof as AHU-1) also rattling.
|
Check | OK | Comments |
---|---|---|
Chilled Water Central Plant | ||
Chiller operational
|
Yes
|
Turned off due to heating season.
|
Cooling tower operational
|
Yes
|
Turned off due to heating season.
|
Heating Central Plant | ||
Boiler operational
|
Yes
|
Misc. Comments
RTU-1 - Access door to the outside air section was completely open and was swinging with wind. Closed and latched it properly while on site.
Work Order Number(s)
264765
Issues found durring this assessment have been assigned to the above
work order(s).