School
Assessor
Hummy Khan
Date
Outdoor Temperature
42°F
Relative Humidity
87%
Outdoor Dew Point
38°F
Air Handling Unit (Assess representative sample of RTU/AHU, including Portables)
Check | OK | Comments |
---|---|---|
Tag Number | ||
Displayed
|
Yes Work Order Closed by Building Maintenance
|
No tag numbers on any exhaust fans except one (EF-26), repeat finding.
|
Status | ||
Running
|
Yes Work Order Closed by Building Maintenance
|
Air handling unit (AHU-11) not running. HV-1 (kitchen) not running, repeat finding.
|
Check | OK | Comments |
---|---|---|
Outdoor Pollution | ||
Free from pollution sources w/i 25 ft. (e.g. dumpster, chimney, etc.)
|
Yes
|
|
Louvers and Access Doors | ||
Operating properly
|
Yes
|
|
Deflectors & Screens | ||
Present
|
Yes
|
|
No debris
|
Yes
|
|
Dampers | ||
Outside air damper: no obstructions
|
Yes Work Order Closed by Building Maintenance
|
AHU-11 - Outside air dampers (OADs) 100% open and return air dampers 100% closed while the unit not running. AHU-2 OADs barely open.
|
Return air damper: no obstructions
|
Yes Work Order Closed by Building Maintenance
|
AHU-11 - Return air dampers 100% closed while the unit not running
|
Check | OK | Comments |
---|---|---|
Clean | ||
No excess dirt, not used for storage
|
Yes
|
|
Insulation | ||
Secure and Clean
|
Yes
|
|
P-Trap (if present) | ||
Charged with liquid
|
Yes
|
Check | OK | Comments |
---|---|---|
Filters | ||
Free of any bypassing
|
Yes Work Order Closed by Building Maintenance
|
AHU-1, AHU-2 and AHU-4 - Air bypass around filters.
|
Correct size
|
Yes Work Order Closed by Building Maintenance
|
AHU-1, AHU-2 and AHU-4 - Incorrect size filters.
|
Free from excessive loading, dampness or odor
|
Yes
|
|
Not collapsed/not fallen off
|
Yes Work Order Closed by Building Maintenance
|
AHU-2 - One filter coming out of the track.
|
Present (not missing)
|
Yes
|
|
Date and initials written
|
Yes Work Order Closed by Building Maintenance
|
AHU-10 and AHU-12- No date/initials of the installing tech on final filter.
|
Heating Coils | ||
Clean, no noticeable leaks, or obstructions
|
Yes
|
|
Cooling Coils | ||
Clean, no noticeable leaks, or obstructions
|
Yes
|
|
Access: Free of any obstructions in area that may affect access
|
Yes
|
|
Condensation: No excess condensation problems
|
Yes
|
|
Blowoff: Free of water from coil blowoff
|
Yes
|
|
Condensate Pan and Drain Line | ||
No visible bacterial or fungal growth
|
Yes
|
|
Clean, no residue, no standing water
|
Yes
|
|
No Overflow, leakage, blockage, or damage
|
Yes
|
|
Proper slope, drain line ok, drainage acceptable, discharge okay
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
Operational
|
Yes Work Order Closed by Building Maintenance
|
Kitchen dishwasher exhaust fan not running even after turning the switch on in the kitchen.
Except for EF-26, none of the exhaust fans running.
|
No unusual odors, noise, or vibration
|
Yes
|
Check | OK | Comments |
---|---|---|
Chilled Water Central Plant | ||
Chiller operational
|
Yes
|
Turned off due to heating season.
|
Cooling tower operational
|
Yes Work Order Closed by Building Maintenance
|
Heavy algae build up due to lack of cleaning and proper chemical treatment as required. Turned off due to heating season,
|
Heating Central Plant | ||
Boiler operational
|
Yes
|
Misc. Comments
Brand new filters laying open on top of HV-1.
Work Order Number(s)
263231
Issues found durring this assessment have been assigned to the above
work order(s).