School
Assessor
Hummy Khan
Date
Outdoor Temperature
42°F
Relative Humidity
79%
Outdoor Dew Point
36°F
Air Handling Unit (Assess representative sample of RTU/AHU, including Portables)
Check | OK | Comments |
---|---|---|
Tag Number | ||
Displayed
|
Yes
|
|
Status | ||
Running
|
Yes
|
Check | OK | Comments |
---|---|---|
Outdoor Pollution | ||
Free from pollution sources w/i 25 ft. (e.g. dumpster, chimney, etc.)
|
Yes
|
|
Louvers and Access Doors | ||
Operating properly
|
Yes
|
|
Deflectors & Screens | ||
Present
|
Yes
|
|
No debris
|
Yes
|
|
Dampers | ||
Outside air damper: no obstructions
|
Yes Work Order Closed by Building Maintenance
|
Inconsistency on the position of the outside air dampers (OADs) from one unit to the other. On some units OADs appear to be 100% open and on others 100% closed. For example, ACU-4, ACU-5, ACU-6, ACU-8, ACU-14 and ACU-2, OADs, 100% open and HV-1, HV-2, ACU-7, ACU-9, and ACU-16 (AAON) 100% closed.
The outside air dampers should not be 100% open on any units when the outside air temperature is in the high 30 degrees to low 40 degrees.
|
Return air damper: no obstructions
|
Yes
|
Check | OK | Comments |
---|---|---|
Clean | ||
No excess dirt, not used for storage
|
Yes Work Order Closed by Building Maintenance
|
On all units, OADs and mixing plenum dirty.
|
Insulation | ||
Secure and Clean
|
Yes
|
|
P-Trap (if present) | ||
Charged with liquid
|
Yes
|
Check | OK | Comments |
---|---|---|
Filters | ||
Free of any bypassing
|
Yes Work Order Closed by Building Maintenance
|
HV-2 - Air bypass around filters due to incorrect size filters.
|
Correct size
|
Yes Work Order Closed by Building Maintenance
|
HV-2- Incorrect size filters.
|
Free from excessive loading, dampness or odor
|
Yes
|
|
Not collapsed/not fallen off
|
Yes
|
|
Present (not missing)
|
Yes
|
|
Date and initials written
|
Yes Work Order Closed by Building Maintenance
|
AHU-16 (AAON)- Filter dated July 2021 and is past due per HCPSS filter change program.
|
Heating Coils | ||
Clean, no noticeable leaks, or obstructions
|
Yes
|
|
Cooling Coils | ||
Clean, no noticeable leaks, or obstructions
|
Yes
|
|
Access: Free of any obstructions in area that may affect access
|
Yes
|
|
Condensation: No excess condensation problems
|
Yes
|
|
Blowoff: Free of water from coil blowoff
|
Yes
|
|
Condensate Pan and Drain Line | ||
No visible bacterial or fungal growth
|
Yes
|
|
Clean, no residue, no standing water
|
Yes
|
|
No Overflow, leakage, blockage, or damage
|
Yes
|
|
Proper slope, drain line ok, drainage acceptable, discharge okay
|
Yes Work Order Closed by Building Maintenance
|
On all units except one (AHU-16 (AAON) the condensate drain improperly terminated, repeat finding.
|
Check | OK | Comments |
---|---|---|
Condition | ||
Operational
|
Yes Work Order Closed by Building Maintenance
|
Exhaust Fan (ERV-7) - Not running.
|
No unusual odors, noise, or vibration
|
Yes Work Order Closed by Building Maintenance
|
Exhaust fan (EF-7) - Rattling. ACU-4-excessive noise, repeat finding.
|
Check | OK | Comments |
---|---|---|
Chilled Water Central Plant | ||
Chiller operational
|
Yes
|
Turned off for the heating season.
|
Cooling tower operational
|
Yes
|
Turned off for the heating season.
|
Heating Central Plant | ||
Boiler operational
|
Yes
|
Check | OK | Comments |
---|---|---|
Thermostat | ||
Thermostat setting acceptable
|
Yes Work Order Closed by Building Maintenance
|
Portable 28- "change air filter" alarm on screen display.
Portable 130- Thermostat heat setting 66 degrees (too low). Should be at least 68 deg. or 70 deg.
|
Thermostat cover
|
Yes
|
|
Fan Mode Correct
|
Yes
|
|
Space Temperature Acceptable
|
Yes
|
Misc. Comments
This is a duplicate report from Lake Elkhorn Middle School since both schools are located in one building. Some findings are applicable to this school and some to Lake Elkhorn Middle School.
Work Order Number(s)
261572
Issues found durring this assessment have been assigned to the above
work order(s).