School
Assessor
Jeffrey Klenk
Date
Air Distribution and Terminal System (Assess 2-3 Locations per HVAC Zone)
Check | OK | Comments |
---|---|---|
Condition | ||
No odors, noise or vibration
|
Yes
|
|
Clean, no obstructions
|
Yes
|
|
Free from signs of moisture/mold, insects or rodents?
|
Yes
|
|
No noticeable air leaks
|
Yes
|
Check | OK | Comments |
---|---|---|
Ceiling Tiles | ||
Tight seal on all tiles
|
Yes
|
|
No stained/damaged tiles indicating high RH or moisture problem
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
No odors or unusual sounds
|
Yes
|
|
Clean, no excess dirt or moisture
|
Yes
|
|
No obstruction to air flow
|
Yes
|
|
No purposely placed obstruction indicating occupant distress
|
Yes
|
|
Location | ||
No short circuiting between supply and return
|
Yes
|
|
Doors | ||
Doors not tight or difficult to close indicating large pressure differential
|
Yes
|
Building
Check | OK | Comments |
---|---|---|
Foundation | ||
No moisture penetration or signs of mold?
|
Yes
|
|
Doors and Windows | ||
Caulking and weather stripping in good condition
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
Room is free of dust and clutter
|
Yes
|
|
No stained or damage ceiling tiles
|
Yes Work Order Closed by Building Maintenance
|
Water stained ceiling tile in girls locker room (at entrance near chalkboard). If not already being addressed, school custodial staff is to submit a work order to Building Services to assess and correct leak.
|
No visible mold present (walls, cabinets, under sinks, behind posters)
|
Yes
|
|
Relative Humidity | ||
Not above 70%
|
Yes Work Order Closed by Building Maintenance
|
Band, choral, and technology education classrooms had 80-85% relative humidity with room temperatures at approximately 73 degrees F. Correspondence sent to Building Services who addressed the issue. Per custodial staff, this was the first day during summer break that the HVAC serving these areas was operating (custodial staff requested due to performing summer cleaning in these areas). Thus no extended period of relative humidity resulting in mold growth.
|
Check | OK | Comments |
---|---|---|
Condition | ||
Clean
|
Yes
|
|
No unusual noise or odor
|
Yes
|
|
No mold growth on insulation
|
Yes
|
|
Traps contain water
|
Yes
|
|
Chemical Storage | ||
Containers capped
|
Yes
|
|
No evidence of an active spill
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
No odors, or unusual noise or vibration
|
Yes Work Order Closed by Building Maintenance
|
Portable 273 was cold inside with a temperature of at least 70 degrees F and 35% relative humidity. Summer setting for air conditioning in portables is to be 82 degrees F. The thermostat set point for cooling indicated 82 degrees F. The other three portables had thermostat set at 82 degrees F and room temperature at 82 degrees F. Work order 247441.
|
Work Order Number(s)
247441
Issues found durring this assessment have been assigned to the above
work order(s).