Assessor
Christopher Madden
Date
Air Distribution and Terminal System (Assess 2-3 Locations per HVAC Zone)
Check | OK | Comments |
---|---|---|
Condition | ||
No odors, noise or vibration
|
Yes
|
|
Clean, no obstructions
|
Yes
|
|
Free from signs of moisture/mold, insects or rodents?
|
Yes
|
|
No noticeable air leaks
|
Yes
|
Check | OK | Comments |
---|---|---|
Ceiling Tiles | ||
Tight seal on all tiles
|
Yes
|
|
No stained/damaged tiles indicating high RH or moisture problem
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
No odors or unusual sounds
|
Yes
|
|
Clean, no excess dirt or moisture
|
Yes
|
|
No obstruction to air flow
|
Yes Work Order Closed by Building Maintenance
|
Room 6, 36, 39, and 44 - Return vents blocked by items (file cabinet, air purifier, boxes, etc.).
|
No purposely placed obstruction indicating occupant distress
|
Yes
|
|
Location | ||
No short circuiting between supply and return
|
Yes
|
|
Doors | ||
Doors not tight or difficult to close indicating large pressure differential
|
Yes
|
Building
Check | OK | Comments |
---|---|---|
Foundation | ||
No moisture penetration or signs of mold?
|
Yes
|
|
Doors and Windows | ||
Caulking and weather stripping in good condition
|
Yes Work Order Closed by Building Maintenance
|
Portable 104 - Door rusted due to moisture intrusion into the door. Building Maintenance is to replace (WO #227566).
|
Check | OK | Comments |
---|---|---|
Condition | ||
Room is free of dust and clutter
|
Yes Work Order Closed by Building Maintenance
|
Room 005 - Clutter.
Room 020 - Moderate clutter on shelves.
Portable 170 - Evidence of ants (WO #227586).
|
No stained or damage ceiling tiles
|
Yes
|
|
No visible mold present (walls, cabinets, under sinks, behind posters)
|
Yes Work Order Closed by Building Maintenance
|
Mold growth observed on drywall ceiling near the return vents is the bathroom next to room 006, the bathroom across from 42, and Room 012. The ceilings were determined to be dry with the use of a moisture meter. • The cause of the mold growth has not been confirmed however, the cause is suspected to be related to elevated relative humidity or thermal differentials in vicinity of the return air vents. Building Maintenance (HVAC) has made adjustments to the HVAC controls in these areas. The impacted areas will be cleaned and encapsulated with a mold inhibiting encapsulant. The impacted areas will be monitored (particularly in the cooling season) by the Office of the Environment to see if the control modifications were effective.
|
Relative Humidity | ||
Not above 70%
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
Clean
|
Yes
|
|
No unusual noise or odor
|
Yes
|
|
No mold growth on insulation
|
Yes
|
|
Traps contain water
|
Yes
|
|
Chemical Storage | ||
Containers capped
|
Yes
|
|
No evidence of an active spill
|
Yes Work Order Closed by Building Maintenance
|
Custodial cleaning container leaking in Kitchen storage area.
|
Check | OK | Comments |
---|---|---|
Condition | ||
No odors, or unusual noise or vibration
|
Yes
|
Work Order Number(s)
227566
Issues found durring this assessment have been assigned to the above
work order(s).