Indoor Environmental Quality General Assessment of Pointers Run Elementary School: January 20th, 2022 (GXPRES202200007D)

Assessor
Christopher Madden
Date

Air Distribution and Terminal System (Assess 2-3 Locations per HVAC Zone)

Ductwork (Supply and Return)
Check OK Comments
Condition
No odors, noise or vibration
Yes
Clean, no obstructions
Yes
Free from signs of moisture/mold, insects or rodents?
Yes
No noticeable air leaks
Yes
Plenum
Check OK Comments
Ceiling Tiles
Tight seal on all tiles
Yes
No stained/damaged tiles indicating high RH or moisture problem
Yes
Supply Diffusers, Return Grilles, Exhaust Grilles
Check OK Comments
Condition
No odors or unusual sounds
Yes
Clean, no excess dirt or moisture
No
Gym Return - Light dust accumulation on the return grille.
No obstruction to air flow
Yes
No purposely placed obstruction indicating occupant distress
Yes
Location
No short circuiting between supply and return
Yes
Doors
Doors not tight or difficult to close indicating large pressure differential
Yes

Building

Envelope
Check OK Comments
Foundation
No moisture penetration or signs of mold?
No
Bulkhead Outside of 47 - Light mold growth on the backside of the drywall associated with a roof leak. See IEQ Concern # for additional information. Note that the Concern report will not be available unit all response actions have been completed.
Doors and Windows
Caulking and weather stripping in good condition
No
Exterior Windows (outside of Art) - Caulk deteriorating and window seal appears to be compromised (WO #220676). Gymnasium - Daylight at exterior door (WO #220675).
Classrooms (Assess 2 to 3 per HVAC System Zone)
Check OK Comments
Condition
Room is free of dust and clutter
Yes
No stained or damage ceiling tiles
No
091 (Pod Storage), Outside of 098, 096, Outside of 74, Outside of 63, and 19 - Stained Ceiling Tile(s) 61 - Stained Ceiling Tile (WO #220676) Staff Lounge - Stained Ceiling Tile due to electrical conduit penetration in roof. Building Services (Roofing) will re-seal per 1/21/2022 communication.
No visible mold present (walls, cabinets, under sinks, behind posters)
Yes
Relative Humidity
Not above 70%
Yes
Mechanical/Boiler Rooms (Assess Each)
Check OK Comments
Condition
Clean
Yes
No unusual noise or odor
Yes
No mold growth on insulation
Yes
Traps contain water
No
Boys Bathroom Across from 56 - Bag on urinal. Urinal should be flushed occasionally so it doesn't dry out.
Chemical Storage
Containers capped
Yes
No evidence of an active spill
Yes
Fan Coil Units/VAV Boxes
Check OK Comments
Condition
No odors, or unusual noise or vibration
Yes