Assessor
Christopher Madden
Date
Air Distribution and Terminal System (Assess 2-3 Locations per HVAC Zone)
Check | OK | Comments |
---|---|---|
Condition | ||
No odors, noise or vibration
|
Yes
|
|
Clean, no obstructions
|
Yes
|
|
Free from signs of moisture/mold, insects or rodents?
|
Yes
|
|
No noticeable air leaks
|
Yes
|
Check | OK | Comments |
---|---|---|
Ceiling Tiles | ||
Tight seal on all tiles
|
Yes
|
|
No stained/damaged tiles indicating high RH or moisture problem
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
No odors or unusual sounds
|
Yes
|
|
Clean, no excess dirt or moisture
|
No
|
Gym Return - Light dust accumulation on the return grille.
|
No obstruction to air flow
|
Yes
|
|
No purposely placed obstruction indicating occupant distress
|
Yes
|
|
Location | ||
No short circuiting between supply and return
|
Yes
|
|
Doors | ||
Doors not tight or difficult to close indicating large pressure differential
|
Yes
|
Building
Check | OK | Comments |
---|---|---|
Foundation | ||
No moisture penetration or signs of mold?
|
No
|
Bulkhead Outside of 47 - Light mold growth on the backside of the drywall associated with a roof leak. See IEQ Concern # for additional information. Note that the Concern report will not be available unit all response actions have been completed.
|
Doors and Windows | ||
Caulking and weather stripping in good condition
|
No
|
Exterior Windows (outside of Art) - Caulk deteriorating and window seal appears to be compromised (WO #220676).
Gymnasium - Daylight at exterior door (WO #220675).
|
Check | OK | Comments |
---|---|---|
Condition | ||
Room is free of dust and clutter
|
Yes
|
|
No stained or damage ceiling tiles
|
No
|
091 (Pod Storage), Outside of 098, 096, Outside of 74, Outside of 63, and 19 - Stained Ceiling Tile(s)
61 - Stained Ceiling Tile (WO #220676)
Staff Lounge - Stained Ceiling Tile due to electrical conduit penetration in roof. Building Services (Roofing) will re-seal per 1/21/2022 communication.
|
No visible mold present (walls, cabinets, under sinks, behind posters)
|
Yes
|
|
Relative Humidity | ||
Not above 70%
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
Clean
|
Yes
|
|
No unusual noise or odor
|
Yes
|
|
No mold growth on insulation
|
Yes
|
|
Traps contain water
|
No
|
Boys Bathroom Across from 56 - Bag on urinal. Urinal should be flushed occasionally so it doesn't dry out.
|
Chemical Storage | ||
Containers capped
|
Yes
|
|
No evidence of an active spill
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
No odors, or unusual noise or vibration
|
Yes
|