School
Assessor
Hummy Khan
Date
Outdoor Temperature
61°F
Relative Humidity
63%
Outdoor Dew Point
48°F
Air Handling Unit (Assess representative sample of RTU/AHU, including Portables)
Check | OK | Comments |
---|---|---|
Tag Number | ||
Displayed
|
Yes Work Order Closed by Building Maintenance
|
No tag numbers on any exhaust fans.
|
Status | ||
Running
|
Yes
|
Check | OK | Comments |
---|---|---|
Outdoor Pollution | ||
Free from pollution sources w/i 25 ft. (e.g. dumpster, chimney, etc.)
|
Yes
|
|
Louvers and Access Doors | ||
Operating properly
|
Yes
|
|
Deflectors & Screens | ||
Present
|
Yes
|
|
No debris
|
Yes
|
|
Dampers | ||
Outside air damper: no obstructions
|
Yes Work Order Closed by Building Maintenance
|
OAHU-2 and OAHU-4- A portion of the outside air dampers appeared to be 100% closed. These are dedicated outside air units and should be capable of bringing in100% outside air all the time while running.
AHU-3 and AHU-5 - Outside air dampers (OADs) appeared to be closed. AHU-6- OADs are open but only slightly.
There seems to be a lot of inconsistency on the position of the outside air dampers. Some are completely closed while others are more open. Today's outdoor weather conditions are ideal for the economizer mode, meaning the OADs should be open more than the minimum position up to 100%.
|
Return air damper: no obstructions
|
Yes
|
Check | OK | Comments |
---|---|---|
Clean | ||
No excess dirt, not used for storage
|
Yes
|
|
Insulation | ||
Secure and Clean
|
Yes
|
|
P-Trap (if present) | ||
Charged with liquid
|
Yes
|
Check | OK | Comments |
---|---|---|
Filters | ||
Free of any bypassing
|
Yes Work Order Closed by Building Maintenance
|
AHU-5- Air bypass around filters.
|
Correct size
|
Yes
|
|
Free from excessive loading, dampness or odor
|
Yes
|
|
Not collapsed/not fallen off
|
Yes Work Order Closed by Building Maintenance
|
OAHU-2 and OAHU-4- Filter fallen off. Tried to put it back on but was not able to do so properly because it is bent. Filter clips missing in OAHU-4.
|
Present (not missing)
|
Yes
|
|
Date and initials written
|
Yes
|
|
Heating Coils | ||
Clean, no noticeable leaks, or obstructions
|
Yes
|
|
Cooling Coils | ||
Clean, no noticeable leaks, or obstructions
|
Yes
|
|
Access: Free of any obstructions in area that may affect access
|
Yes
|
|
Condensation: No excess condensation problems
|
Yes
|
|
Blowoff: Free of water from coil blowoff
|
Yes
|
|
Condensate Pan and Drain Line | ||
No visible bacterial or fungal growth
|
Yes
|
|
Clean, no residue, no standing water
|
Yes
|
|
No Overflow, leakage, blockage, or damage
|
Yes
|
|
Proper slope, drain line ok, drainage acceptable, discharge okay
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
Operational
|
Yes Work Order Closed by Building Maintenance
|
Exhaust fan (no tag number) located near OAHU-3 - Not running.
|
No unusual odors, noise, or vibration
|
Yes Work Order Closed by Building Maintenance
|
Exhaust fan (no tag number) located near AHU-6 and another exhaust near cooling tower - Excessive vibration.
|
Check | OK | Comments |
---|---|---|
Chilled Water Central Plant | ||
Chiller operational
|
Yes
|
|
Cooling tower operational
|
Yes
|
|
Heating Central Plant | ||
Boiler operational
|
Yes
|
Check | OK | Comments |
---|---|---|
Thermostat | ||
Thermostat setting acceptable
|
Yes
|
|
Thermostat cover
|
Yes
|
|
Fan Mode Correct
|
Yes
|
|
Space Temperature Acceptable
|
Yes
|
Work Order Number(s)
215031
Issues found durring this assessment have been assigned to the above
work order(s).