School
Assessor
Hummy Khan
Date
Outdoor Temperature
54°F
Relative Humidity
83%
Outdoor Dew Point
48°F
Air Handling Unit (Assess representative sample of RTU/AHU, including Portables)
Check | OK | Comments |
---|---|---|
Tag Number | ||
Displayed
|
Yes Work Order Closed by Building Maintenance
|
No tag numbers on any exhaust fans.
|
Status | ||
Running
|
Yes Work Order Closed by Building Maintenance
|
RTU-1 and RTU-4 - Not running. Notified Building Maintenance HVAC while on site. Several exhaust fans not running.
|
Check | OK | Comments |
---|---|---|
Outdoor Pollution | ||
Free from pollution sources w/i 25 ft. (e.g. dumpster, chimney, etc.)
|
Yes
|
|
Louvers and Access Doors | ||
Operating properly
|
Yes Work Order Closed by Building Maintenance
|
On RTU-2, the handle lever to open up the outside air damper/relief fan section on one side of unit is bent.
|
Deflectors & Screens | ||
Present
|
Yes Work Order Closed by Building Maintenance
|
|
No debris
|
Yes
|
|
Dampers | ||
Outside air damper: no obstructions
|
Yes Work Order Closed by Building Maintenance
|
The outside air dampers (OADs) on all units appeared to have been open at minimum position. Based on today's outside weather condition the OADs could have been opened in economizer mode, meaning maximizing introduction of outside air while minimizing energy usage. The operation of economizer mode on all units should be checked and verified by actual demonstration in the field.
|
Return air damper: no obstructions
|
Yes
|
Check | OK | Comments |
---|---|---|
Clean | ||
No excess dirt, not used for storage
|
Yes
|
|
Insulation | ||
Secure and Clean
|
Yes
|
|
P-Trap (if present) | ||
Charged with liquid
|
Yes
|
Check | OK | Comments |
---|---|---|
Filters | ||
Free of any bypassing
|
Yes Work Order Closed by Building Maintenance
|
RTU-1 - Wood pieces used as a blank cover has air bypass. Use same size wood pieces as RTU-2 to prevent air bypass.
|
Correct size
|
Yes
|
|
Free from excessive loading, dampness or odor
|
Yes
|
|
Not collapsed/not fallen off
|
Yes Work Order Closed by Building Maintenance
|
RTU-4 - One filter was installed in the wrong direction and was corrected while on site.
|
Present (not missing)
|
Yes
|
|
Date and initials written
|
Yes
|
|
Heating Coils | ||
Clean, no noticeable leaks, or obstructions
|
Yes
|
|
Cooling Coils | ||
Clean, no noticeable leaks, or obstructions
|
Yes
|
|
Access: Free of any obstructions in area that may affect access
|
Yes
|
|
Condensation: No excess condensation problems
|
Yes
|
|
Blowoff: Free of water from coil blowoff
|
Yes
|
|
Condensate Pan and Drain Line | ||
No visible bacterial or fungal growth
|
Yes
|
|
Clean, no residue, no standing water
|
Yes
|
|
No Overflow, leakage, blockage, or damage
|
Yes
|
|
Proper slope, drain line ok, drainage acceptable, discharge okay
|
Yes Work Order Closed by Building Maintenance
|
Condensate drain on all units improperly terminated.
|
Check | OK | Comments |
---|---|---|
Condition | ||
Operational
|
Yes
|
|
No unusual odors, noise, or vibration
|
Yes
|
Check | OK | Comments |
---|---|---|
Heating Central Plant | ||
Boiler operational
|
Yes
|
Check | OK | Comments |
---|---|---|
Thermostat | ||
Thermostat setting acceptable
|
Yes Work Order Closed by Building Maintenance
|
Portable 60- Thermostat screen display blank. Notified Building Maintenance HVAC while on site.
|
Thermostat cover
|
Yes
|
|
Fan Mode Correct
|
Yes
|
|
Space Temperature Acceptable
|
Yes Work Order Closed by Building Maintenance
|
Portable 166- Cooling set at 70 deg. Should be 74 deg.
|
Misc. Comments
Was not able to inspect one rooftop unit and few exhaust fans on the lower roof due to inaccessibility to the lower roof because there is no means to get from higher roof to lower roof (ladder removed during roofing project (Building Maintenance has been notified)).
Work Order Number(s)
207713
Issues found durring this assessment have been assigned to the above
work order(s).