Assessor
Christopher Madden
Date
Air Distribution and Terminal System (Assess 2-3 Locations per HVAC Zone)
Check | OK | Comments |
---|---|---|
Condition | ||
No odors, noise or vibration
|
Yes
|
|
Clean, no obstructions
|
Yes
|
|
Free from signs of moisture/mold, insects or rodents?
|
Yes
|
|
No noticeable air leaks
|
Yes
|
Check | OK | Comments |
---|---|---|
Ceiling Tiles | ||
Tight seal on all tiles
|
Yes
|
|
No stained/damaged tiles indicating high RH or moisture problem
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
No odors or unusual sounds
|
Yes
|
|
Clean, no excess dirt or moisture
|
Yes
|
|
No obstruction to air flow
|
No
|
Art - Paint booth/hood filter overloaded (WO # 205575).
|
No purposely placed obstruction indicating occupant distress
|
Yes
|
|
Location | ||
No short circuiting between supply and return
|
Yes
|
|
Doors | ||
Doors not tight or difficult to close indicating large pressure differential
|
Yes
|
Building
Check | OK | Comments |
---|---|---|
Foundation | ||
No moisture penetration or signs of mold?
|
No
|
208 - Flaking Paint indicative of moisture intrusion (WO #205429).
|
Doors and Windows | ||
Caulking and weather stripping in good condition
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
Room is free of dust and clutter
|
No
|
Art (Back Cabinet), 108 (Window Sill), 109 (Window Sill), 110 (Window Sill) - Dust/debris and or cob webs.
|
No stained or damage ceiling tiles
|
No
|
Custodial Storage (off of custodial office), 127, Band Office, Outside of 122, Fitness Lab, FACS Pantry, Art Storage Closet, 117A, Restroom Across from 102, 148 - Stained Ceiling Tile(s) Kitchen Locker Room - Drywall Staining, no elevated moisture was detected (WO #205406).
|
No visible mold present (walls, cabinets, under sinks, behind posters)
|
Yes
|
|
Relative Humidity | ||
Not above 70%
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
Clean
|
No
|
Compressor leaking with mechanical room. (informed HVAC upon discovery). Penthouse across from Band - Housekeeping.
|
No unusual noise or odor
|
Yes
|
|
No mold growth on insulation
|
No
|
Stage - Water stained pipe insulation (hot water, WO #205421). No visible mold growth observed.
|
Traps contain water
|
Yes
|
|
Chemical Storage | ||
Containers capped
|
Yes
|
|
No evidence of an active spill
|
No
|
Mechanical Penthouse above locker banks - Water leaking from air handling units (HVAC notified upon discovery).
|
Check | OK | Comments |
---|---|---|
Condition | ||
No odors, or unusual noise or vibration
|
Yes
|