Air Distribution and Terminal System (Assess 2-3 Locations per HVAC Zone)
Check | OK | Comments |
---|---|---|
Condition | ||
No odors, noise or vibration
|
Yes
|
|
Clean, no obstructions
|
Yes
|
|
Free from signs of moisture/mold, insects or rodents?
|
Yes
|
|
No noticeable air leaks
|
Yes
|
Check | OK | Comments |
---|---|---|
Ceiling Tiles | ||
Tight seal on all tiles
|
No
|
81 - Ceiling tile bowed out of place. 21 - Tile bowed out of place. Adjusted while onsite. If it comes out of place again, replace. 68 - Missing ceiling tile.128 - Ceiling tile out of place above stage stairs.
|
No stained/damaged tiles indicating high RH or moisture problem
|
No
|
Bowed Ceiling Tiles in various locations throughout facility indicating elevated relative humidity (most likely occurs July-September). Building Maintenance is aware and is planning a controls upgrade project to address the issue, pending available funding.
|
Check | OK | Comments |
---|---|---|
Condition | ||
No odors or unusual sounds
|
Yes
|
|
Clean, no excess dirt or moisture
|
No
|
FACS Storage - Supply diffuser dirty. Kitchen (Dishwashing) - Supply diffuser rusted (WO #205355).
|
No obstruction to air flow
|
No
|
Room 22 - Return air grille blocked.
|
No purposely placed obstruction indicating occupant distress
|
Yes
|
|
Location | ||
No short circuiting between supply and return
|
Yes
|
|
Doors | ||
Doors not tight or difficult to close indicating large pressure differential
|
Yes
|
Building
Check | OK | Comments |
---|---|---|
Foundation | ||
No moisture penetration or signs of mold?
|
No
|
Industrial Arts Storage (S10) - Stair-step cracking in block and damaged drywall (WO #205357). Industrial Arts Storage (131) - Salts on roof deck (WO #205357).
|
Doors and Windows | ||
Caulking and weather stripping in good condition
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
Room is free of dust and clutter
|
No
|
FACS Storage Closet - Dirt/Debris behind washer and drier.
|
No stained or damage ceiling tiles
|
No
|
18 - Hole in corner of tile (above teacher desk). Outside of 13 (above Locker 456), 41 (2 tiles), 67 (minor), 89 - Stained Ceiling Tile(s)
|
No visible mold present (walls, cabinets, under sinks, behind posters)
|
No
|
Relative humidity mold was observed on the inside of the cabinet doors in Rooms 18, 75 , and 89. The doors were cleaned/disinfected upon discovery. Building Maintenance (Plumbing) assessed the fixture in these areas and did not identify any deficiencies with leaks/moisture. Additionally, relative humidity mold growth was observed on a tool cabinet in Room 180. Custodial Services cleaned/disinfected the mold growth in Room 180.
|
Relative Humidity | ||
Not above 70%
|
No
|
Room 007, Cafeteria, 68 (room also too cold) - Building Maintenance is aware and is planning a controls upgrade project to address the issue, pending available funding.
|
Check | OK | Comments |
---|---|---|
Condition | ||
Clean
|
Yes
|
|
No unusual noise or odor
|
Yes
|
|
No mold growth on insulation
|
Yes
|
|
Traps contain water
|
Yes
|
|
Chemical Storage | ||
Containers capped
|
Yes
|
|
No evidence of an active spill
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
No odors, or unusual noise or vibration
|
Yes
|