School
Assessor
Jeffrey Klenk
Date
Air Distribution and Terminal System (Assess 2-3 Locations per HVAC Zone)
Check | OK | Comments |
---|---|---|
Condition | ||
No odors, noise or vibration
|
Yes
|
|
Clean, no obstructions
|
Yes
|
|
Free from signs of moisture/mold, insects or rodents?
|
Yes
|
|
No noticeable air leaks
|
Yes
|
Check | OK | Comments |
---|---|---|
Ceiling Tiles | ||
Tight seal on all tiles
|
Yes
|
|
No stained/damaged tiles indicating high RH or moisture problem
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
No odors or unusual sounds
|
Yes
|
|
Clean, no excess dirt or moisture
|
Yes
|
|
No obstruction to air flow
|
No
|
Air return grille in room B36 was obstructed by a large stack of chairs. School custodial staff is to move chairs and ensure ample free space in front of the air return grille.
|
No purposely placed obstruction indicating occupant distress
|
Yes
|
|
Location | ||
No short circuiting between supply and return
|
Yes
|
|
Doors | ||
Doors not tight or difficult to close indicating large pressure differential
|
Yes
|
Building
Check | OK | Comments |
---|---|---|
Foundation | ||
No moisture penetration or signs of mold?
|
No
|
The carpet flooring in B36 was damp the first 10 square feet of the door. Source was not readily identified except a failed carpet seam. Work Order 201411.
|
Doors and Windows | ||
Caulking and weather stripping in good condition
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
Room is free of dust and clutter
|
Yes
|
|
No stained or damage ceiling tiles
|
No
|
A small ceiling tile was missing in room A67. Custodial staff is to replace or submit a work order for Building Services to special cut a ceiling tile.
|
No visible mold present (walls, cabinets, under sinks, behind posters)
|
No
|
Mold growth observed on piano cover located on stage. School was instructed, to disinfect by wiping, laundering, or discarding.
|
Relative Humidity | ||
Not above 70%
|
No
|
The majority of areas visited were over 70% and up to 80%. HVAC was in operation and indoor temperatures approximately 74 degrees. Includes rooms B13, A43, A67, A33, A27, B36, A20, A57, 206, 212, and 249. Cafeteria room temperature was too cool at 68 degrees with a relative humidity of 66%. Work Order 201401.
|
Check | OK | Comments |
---|---|---|
Condition | ||
Clean
|
Yes
|
|
No unusual noise or odor
|
Yes
|
|
No mold growth on insulation
|
No
|
The pipe insulation of a hot water tank in the laundry room between the locker rooms has a seam that is damp with brown staining and a black blemish. Work Order 201413.
|
Traps contain water
|
Yes
|
|
Chemical Storage | ||
Containers capped
|
Yes
|
|
No evidence of an active spill
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
No odors, or unusual noise or vibration
|
Yes
|