School
Assessor
Christopher Madden
Date
Air Distribution and Terminal System (Assess 2-3 Locations per HVAC Zone)
Check | OK | Comments |
---|---|---|
Condition | ||
No odors, noise or vibration
|
Yes
|
|
Clean, no obstructions
|
Yes
|
|
Free from signs of moisture/mold, insects or rodents?
|
Yes
|
|
No noticeable air leaks
|
Yes
|
Check | OK | Comments |
---|---|---|
Ceiling Tiles | ||
Tight seal on all tiles
|
No
|
310 and Band Equipment Storage - Ceiling tile out of place.
|
No stained/damaged tiles indicating high RH or moisture problem
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
No odors or unusual sounds
|
Yes
|
|
Clean, no excess dirt or moisture
|
No
|
Cafeteria and 707 - Mild dust build up on supply diffusers.
|
No obstruction to air flow
|
Yes
|
|
No purposely placed obstruction indicating occupant distress
|
Yes
|
|
Location | ||
No short circuiting between supply and return
|
Yes
|
|
Doors | ||
Doors not tight or difficult to close indicating large pressure differential
|
Yes
|
Building
Check | OK | Comments |
---|---|---|
Foundation | ||
No moisture penetration or signs of mold?
|
Yes
|
|
Doors and Windows | ||
Caulking and weather stripping in good condition
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
Room is free of dust and clutter
|
No
|
205 - Chalk tray needs to be cleaned. 806 - Cobwebs on windows. FACS Storage - Dead bug in light.
|
No stained or damage ceiling tiles
|
No
|
Science Chemical Storage Room, 310, Outside 309, 406 (2 tiles), 407, 700, FACS, Outside FACS, 707 Storage (2 tiles), 601 - Stained Ceiling Tile(s)
|
No visible mold present (walls, cabinets, under sinks, behind posters)
|
No
|
808 and 809 - Significant relative humidity mold on wooden cabinets in both rooms (served by the same air handling unit). See IEQ Concern CXOMHS20210001C9.
|
Relative Humidity | ||
Not above 70%
|
No
|
808 and 809 - Relative humidity 75.7-76.4%. See IEQ Concern CXOMHS20210001C9.
|
Check | OK | Comments |
---|---|---|
Condition | ||
Clean
|
Yes
|
|
No unusual noise or odor
|
Yes
|
|
No mold growth on insulation
|
Yes
|
|
Traps contain water
|
Yes
|
|
Chemical Storage | ||
Containers capped
|
Yes
|
|
No evidence of an active spill
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
No odors, or unusual noise or vibration
|
Yes
|