School
Assessor
Christopher Madden
Date
Air Distribution and Terminal System (Assess 2-3 Locations per HVAC Zone)
Check | OK | Comments |
---|---|---|
Condition | ||
No odors, noise or vibration
|
No
|
Portable 50, 215, and 122 - Thermostat set to fan "on" which can lead to relative humidity mold growth (WO #198664). Room 339 - Exhaust fan rattling (check belts, bearings, etc., WO #198666).
|
Clean, no obstructions
|
Yes
|
|
Free from signs of moisture/mold, insects or rodents?
|
Yes
|
|
No noticeable air leaks
|
Yes
|
Check | OK | Comments |
---|---|---|
Ceiling Tiles | ||
Tight seal on all tiles
|
No
|
Foreign Language Portable - Several ceiling tiles not fitting properly.
|
No stained/damaged tiles indicating high RH or moisture problem
|
No
|
3rd Floor - Various Areas with Bowed Ceiling Tiles. The 3rd Floor is prone to elevated humidity in the summer (HVAC Contacted).
|
Check | OK | Comments |
---|---|---|
Condition | ||
No odors or unusual sounds
|
Yes
|
|
Clean, no excess dirt or moisture
|
No
|
Dance Studio - Supply Diffusers Dirty (High Dusting Required).
|
No obstruction to air flow
|
Yes
|
|
No purposely placed obstruction indicating occupant distress
|
Yes
|
|
Location | ||
No short circuiting between supply and return
|
Yes
|
|
Doors | ||
Doors not tight or difficult to close indicating large pressure differential
|
Yes
|
Building
Check | OK | Comments |
---|---|---|
Foundation | ||
No moisture penetration or signs of mold?
|
Yes
|
|
Doors and Windows | ||
Caulking and weather stripping in good condition
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
Room is free of dust and clutter
|
No
|
B105 - There are two baked potatoes on a work bench that need to be discarded before they rot.
|
No stained or damage ceiling tiles
|
No
|
Outside 356, 335B, and Media (along TV Studio Wall) - Stained Ceiling Tile(s).
|
No visible mold present (walls, cabinets, under sinks, behind posters)
|
Yes
|
|
Relative Humidity | ||
Not above 70%
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
Clean
|
Yes
|
|
No unusual noise or odor
|
Yes
|
|
No mold growth on insulation
|
Yes
|
|
Traps contain water
|
Yes
|
|
Chemical Storage | ||
Containers capped
|
Yes
|
|
No evidence of an active spill
|
No
|
353 - Sink continues to run even-though off (WO #198666).
|
Check | OK | Comments |
---|---|---|
Condition | ||
No odors, or unusual noise or vibration
|
No
|
The Unit Ventilators on the 1st, 2nd, and 3rd Floor were operational which can lead to elevated humidity in the Summer (HVAC Contacted).
|