School
Assessor
Christopher Madden
Date
Air Distribution and Terminal System (Assess 2-3 Locations per HVAC Zone)
Check | OK | Comments |
---|---|---|
Condition | ||
No odors, noise or vibration
|
Yes
|
|
Clean, no obstructions
|
No
|
Back of Auditorium - Dirty supply diffusers.
|
Free from signs of moisture/mold, insects or rodents?
|
Yes
|
|
No noticeable air leaks
|
Yes
|
Check | OK | Comments |
---|---|---|
Ceiling Tiles | ||
Tight seal on all tiles
|
Yes
|
|
No stained/damaged tiles indicating high RH or moisture problem
|
No
|
200-Level, B-wing - Numerous bowed tiles and elevated humidity noted. Data loggers will be deployed to further investigate.
|
Check | OK | Comments |
---|---|---|
Condition | ||
No odors or unusual sounds
|
Yes
|
|
Clean, no excess dirt or moisture
|
Yes
|
|
No obstruction to air flow
|
Yes
|
|
No purposely placed obstruction indicating occupant distress
|
Yes
|
|
Location | ||
No short circuiting between supply and return
|
Yes
|
|
Doors | ||
Doors not tight or difficult to close indicating large pressure differential
|
Yes
|
Building
Check | OK | Comments |
---|---|---|
Foundation | ||
No moisture penetration or signs of mold?
|
No
|
B108 - Crack in mechanical room wall (WO #196098).
|
Doors and Windows | ||
Caulking and weather stripping in good condition
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
Room is free of dust and clutter
|
No
|
B122 - Non-issued furniture.
|
No stained or damage ceiling tiles
|
No
|
F120, F134, F103, Outside F104, B113, Between 106 and 108 (Main Hall), Cafeteria (above window, across from kitchen), Outside C014, Outside D106, B209 (multiple), B206 (remove due to mold), Main Entrance, Various in 200-level N Hallway, Outside A206 - Stained Ceiling Tile(s). F105 - Hole in ceiling tile. Outside 204 - Broken Ceiling Tile.
|
No visible mold present (walls, cabinets, under sinks, behind posters)
|
Yes
|
|
Relative Humidity | ||
Not above 70%
|
No
|
Auditorium (78.7%) and 200-Level B-Wing (71.3-73.2%) - Data loggers will be deployed to further monitor and determine further action.
|
Check | OK | Comments |
---|---|---|
Condition | ||
Clean
|
No
|
Boiler Room off Media Center - Active leak from valve (WO #196098). Fire Suppression Closet (F138) - Active Leak, significant amount of water on floor (WO #196102).
|
No unusual noise or odor
|
Yes
|
|
No mold growth on insulation
|
No
|
A106 (Mechanical Closet) - Fiberglass pipe insulation deteriorating (WO #196102).
|
Traps contain water
|
Yes
|
|
Chemical Storage | ||
Containers capped
|
Yes
|
|
No evidence of an active spill
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
No odors, or unusual noise or vibration
|
No
|
B113 (FCU59) - Excessive rattle (WO #196104).
|