Indoor Environmental Quality HVAC Assessment of Glenwood Middle School: March 10th, 2021 (HXXGMS202100003B)

Assessor
Hummy Khan
Date
Outdoor Temperature
64°F
Relative Humidity
30%
Outdoor Dew Point
32°F

Air Handling Unit (Assess representative sample of RTU/AHU, including Portables)

Unit
Check OK Comments
Tag Number
Displayed
Yes
Status
Running
Yes
Outdoor Air Intake and Outdoor Air Dampers
Check OK Comments
Outdoor Pollution
Free from pollution sources w/i 25 ft. (e.g. dumpster, chimney, etc.)
Yes
Louvers and Access Doors
Operating properly
Yes
Deflectors & Screens
Present
Yes
No debris
Yes
Dampers
Outside air damper: no obstructions
No
OAU-2-Outside air dampers or return air dampers appear to be closed (assessor unable to determine if the dampers are outdoor or return).
Return air damper: no obstructions
Yes
Mixing Plenum
Check OK Comments
Clean
No excess dirt, not used for storage
No
OAU-4- Ladder stored in the mixing plenum.
Insulation
Secure and Clean
Yes
P-Trap (if present)
Charged with liquid
Yes
Filters and Coils
Check OK Comments
Filters
Free of any bypassing
Yes
Correct size
Yes
Free from excessive loading, dampness or odor
Yes
Not collapsed/not fallen off
No
RTU-1- One filter fallen off. Tried to put it back on multiple times but it keeps falling due to air pressure, needs clips.
Present (not missing)
Yes
Date and initials written
Yes
Heating Coils
Clean, no noticeable leaks, or obstructions
Yes
Cooling Coils
Clean, no noticeable leaks, or obstructions
Yes
Access: Free of any obstructions in area that may affect access
Yes
Condensation: No excess condensation problems
Yes
Blowoff: Free of water from coil blowoff
Yes
Condensate Pan and Drain Line
No visible bacterial or fungal growth
Yes
Clean, no residue, no standing water
Yes
No Overflow, leakage, blockage, or damage
Yes
Proper slope, drain line ok, drainage acceptable, discharge okay
No
OAU-2- Condensate drain terminated away from roof drain.
Fans and Motors
Check OK Comments
Condition
Operational
No
EF-14, EF-15 and EF-17 not running.
No unusual odors, noise, or vibration
No
EF-8, EF-10, EF-12 and EF-13 noisy.
Central Plant
Check OK Comments
Heating Central Plant
Boiler operational
Yes
Misc. Comments
Work Order: 185545
Work Order Number(s)
185545
Issues found durring this assessment have been assigned to the above work order(s).