Indoor Environmental Quality General Assessment of Reservoir High School: March 17th, 2021 (GXXRHS202100003B)

Assessor
Christopher Madden
Date

Air Distribution and Terminal System (Assess 2-3 Locations per HVAC Zone)

Ductwork (Supply and Return)
Check OK Comments
Condition
No odors, noise or vibration
Yes
Clean, no obstructions
Yes
Free from signs of moisture/mold, insects or rodents?
Yes
No noticeable air leaks
Yes
Plenum
Check OK Comments
Ceiling Tiles
Tight seal on all tiles
Yes
No stained/damaged tiles indicating high RH or moisture problem
Yes
Insulation & Fireproofing
Condition okay
No
Cafeteria - Water Damaged Bulkhead. Drywall to be removed (WO #184688). A small amount of fireproofing has been dislodged from the leak.
Supply Diffusers, Return Grilles, Exhaust Grilles
Check OK Comments
Condition
No odors or unusual sounds
Yes
Clean, no excess dirt or moisture
Yes
No obstruction to air flow
Yes
No purposely placed obstruction indicating occupant distress
Yes
Location
No short circuiting between supply and return
Yes
Doors
Doors not tight or difficult to close indicating large pressure differential
Yes

Building

Envelope
Check OK Comments
Foundation
No moisture penetration or signs of mold?
Yes
Doors and Windows
Caulking and weather stripping in good condition
Yes
Classrooms (Assess 2 to 3 per HVAC System Zone)
Check OK Comments
Condition
Room is free of dust and clutter
No
Room 300 - Mini Fridge and microwave. Room 333 - Two lamps, curtains, and a majority of the walls are covered with posters, etc. (fire hazard). Room 327 - Mini-fridge. Room 322 - Curtains. Room 206 - Two lamps. Room 230 - Plastic screening and PVC enclosure represents potential fire hazard. Room 221 - Curtains, lamp, refrigerator, and microwave.
No stained or damage ceiling tiles
No
Cafeteria - Water Damaged Bulkhead. Drywall to be removed (WO #184688). Weight Room (Back Left), S-17, and Main Hall (Across from 108) Stained Ceiling Tile(s)
No visible mold present (walls, cabinets, under sinks, behind posters)
Yes
Relative Humidity
Not above 70%
Yes
Mechanical/Boiler Rooms (Assess Each)
Check OK Comments
Condition
Clean
Yes
The mechanical and electrical rooms were extremely clean.
No unusual noise or odor
Yes
No mold growth on insulation
Yes
Traps contain water
Yes
Chemical Storage
Containers capped
Yes
No evidence of an active spill
Yes
Fan Coil Units/VAV Boxes
Check OK Comments
Condition
No odors, or unusual noise or vibration
No
Room 335 - The unit ventilator was not running. All other inspected rooms were running. (WO #184689).