School
Assessor
Jeffrey Klenk
Date
Air Distribution and Terminal System (Assess 2-3 Locations per HVAC Zone)
Check | OK | Comments |
---|---|---|
Condition | ||
No odors, noise or vibration
|
Yes
|
|
Clean, no obstructions
|
Yes
|
|
Free from signs of moisture/mold, insects or rodents?
|
Yes
|
|
No noticeable air leaks
|
Yes
|
Check | OK | Comments |
---|---|---|
Ceiling Tiles | ||
Tight seal on all tiles
|
Yes
|
|
No stained/damaged tiles indicating high RH or moisture problem
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
No odors or unusual sounds
|
Yes
|
|
Clean, no excess dirt or moisture
|
Yes
|
|
No obstruction to air flow
|
No
|
Air flow was not sensed from the supply air diffusers in rooms 62, 78, and 206A. Rooms 62 and 78 share the same ventilation unit / zone while 206A has its own unit. Findings were discussed with the school's HVAC mechanic who happened to be on site. The HVAC Shop is aware of unit PRTU 101 tripping off over a cold weekend and in the process of diagnosing. The HVAC mechanic receives an alarm to know PRTU has shut down. The mechanic was in the process of physically turning the unit back on. The HVAC mechanic checked the unit serving 206A. The unit was found to be working. The unit may have cycled on later than other units and after the interior inspection of room 206A.
|
No purposely placed obstruction indicating occupant distress
|
Yes
|
|
Location | ||
No short circuiting between supply and return
|
Yes
|
|
Doors | ||
Doors not tight or difficult to close indicating large pressure differential
|
Yes
|
Building
Check | OK | Comments |
---|---|---|
Foundation | ||
No moisture penetration or signs of mold?
|
Yes
|
|
Doors and Windows | ||
Caulking and weather stripping in good condition
|
No
|
Portable 78. While probing a previous (repaired) water intrusion incident around a window, the teacher indicated the window continues to leak during heavy rains. No signs of moisture were observed or detected with a moisture meter at the time of the inspection. Work Order 183360.
|
Check | OK | Comments |
---|---|---|
Condition | ||
Room is free of dust and clutter
|
No
|
An odor was detected in room 132. The odor was from scented oil wicking sticks. Teacher was informed. School administration is to remind staff air fresheners of any type are not permitted.
|
No stained or damage ceiling tiles
|
No
|
Water stained ceiling tiles observed in room 51, 96 (few in storage closet), and the hallway near the water fountain located between second and third grade pods. Custodial staff is to submit a work order to Building Services if not already being addressed.
|
No visible mold present (walls, cabinets, under sinks, behind posters)
|
Yes
|
|
Relative Humidity | ||
Not above 70%
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
Clean
|
Yes
|
|
No unusual noise or odor
|
Yes
|
|
No mold growth on insulation
|
Yes
|
|
Traps contain water
|
Yes
|
|
Chemical Storage | ||
Containers capped
|
Yes
|
|
No evidence of an active spill
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
No odors, or unusual noise or vibration
|
No
|
The thermostat in portable 143 displayed "replace battery". Work Order 183350.
|