Assessor
Hummy Khan
Date
Outdoor Temperature
41°F
Relative Humidity
52%
Outdoor Dew Point
25°F
Air Handling Unit (Assess representative sample of RTU/AHU, including Portables)
Check | OK | Comments |
---|---|---|
Tag Number | ||
Displayed
|
Yes
|
|
Status | ||
Running
|
No
|
RAHU-6 and ICE (MUAU-1) not running. Informed the HVAC department while on site.
|
Check | OK | Comments |
---|---|---|
Outdoor Pollution | ||
Free from pollution sources w/i 25 ft. (e.g. dumpster, chimney, etc.)
|
Yes
|
|
Louvers and Access Doors | ||
Operating properly
|
Yes
|
|
Deflectors & Screens | ||
Present
|
Yes
|
|
No debris
|
Yes
|
|
Dampers | ||
Outside air damper: no obstructions
|
No
|
RAHU-7 - Outside air dampers appear to be closed.
|
Return air damper: no obstructions
|
Yes
|
Check | OK | Comments |
---|---|---|
Clean | ||
No excess dirt, not used for storage
|
No
|
ERU-1- A spare filter laying inside the unit in the outside air intake section.
|
Insulation | ||
Secure and Clean
|
Yes
|
|
P-Trap (if present) | ||
Charged with liquid
|
Yes
|
Check | OK | Comments |
---|---|---|
Filters | ||
Free of any bypassing
|
No
|
RAHU-12 -Filters missing creating bypass. ERU-2 - Air bypass around filters.
|
Correct size
|
No
|
RAHU-2 and 5 - Incorrect size filters installed on multiple racks.
|
Free from excessive loading, dampness or odor
|
Yes
|
|
Not collapsed/not fallen off
|
Yes
|
|
Present (not missing)
|
No
|
RAHU-12 - At least one filter missing on each rack from a total of three racks creating openings for bypass. RAHU-11- The entire set of pre-filters and majority of the final filters are missing.
|
Date and initials written
|
No
|
RAHU-6, RHU-8 and 9 - No dates and initials of installing technician on the filters.
|
Heating Coils | ||
Clean, no noticeable leaks, or obstructions
|
Yes
|
|
Cooling Coils | ||
Clean, no noticeable leaks, or obstructions
|
Yes
|
|
Access: Free of any obstructions in area that may affect access
|
Yes
|
|
Condensation: No excess condensation problems
|
Yes
|
|
Blowoff: Free of water from coil blowoff
|
Yes
|
|
Condensate Pan and Drain Line | ||
No visible bacterial or fungal growth
|
Yes
|
|
Clean, no residue, no standing water
|
Yes
|
|
No Overflow, leakage, blockage, or damage
|
Yes
|
|
Proper slope, drain line ok, drainage acceptable, discharge okay
|
No
|
Condensate drain on all rooftop units improperly terminated.
|
Check | OK | Comments |
---|---|---|
Condition | ||
Operational
|
No
|
Exhaust fan-1, 2, 3, 4, 14, 17, 31, 33, 34 and 37 not running.
|
No unusual odors, noise, or vibration
|
Yes
|
Check | OK | Comments |
---|---|---|
Heating Central Plant | ||
Boiler operational
|
Yes
|
Work Order Number(s)
180977
Issues found durring this assessment have been assigned to the above
work order(s).
Building Maintenance (HVAC) visited the site on February 23 to further assess and have issues corrected.
Work Order: 180977