Indoor Environmental Quality HVAC Assessment of Hanover Hills Elementary School: January 8th, 2021 (HXHHES2021000029)

Assessor
Christopher Madden
Date
Outdoor Temperature
34°F
Relative Humidity
64%
Outdoor Dew Point
23°F

Air Handling Unit (Assess representative sample of RTU/AHU, including Portables)

Unit
Check OK Comments
Tag Number
Displayed
Yes
Status
Running
No
DOAS - 3 - Not operational, freeze stat tripped.
Outdoor Air Intake and Outdoor Air Dampers
Check OK Comments
Outdoor Pollution
Free from pollution sources w/i 25 ft. (e.g. dumpster, chimney, etc.)
Yes
Louvers and Access Doors
Operating properly
Yes
Deflectors & Screens
Present
Yes
No debris
Yes
Dampers
Outside air damper: no obstructions
Yes
Return air damper: no obstructions
Yes
Mixing Plenum
Check OK Comments
Clean
No excess dirt, not used for storage
Yes
Insulation
Secure and Clean
Yes
P-Trap (if present)
Charged with liquid
Yes
Filters and Coils
Check OK Comments
Filters
Free of any bypassing
Yes
Correct size
Yes
Free from excessive loading, dampness or odor
Yes
Not collapsed/not fallen off
Yes
Present (not missing)
Yes
Date and initials written
Yes
Heating Coils
Clean, no noticeable leaks, or obstructions
No
DOAS 1 - Paper/Document stuck to coils. Appeared to have been adhered within unit and dislodged. Removed while onsite.
Cooling Coils
Clean, no noticeable leaks, or obstructions
Yes
Access: Free of any obstructions in area that may affect access
Yes
Condensation: No excess condensation problems
Yes
Blowoff: Free of water from coil blowoff
Yes
Condensate Pan and Drain Line
No visible bacterial or fungal growth
Yes
Clean, no residue, no standing water
Yes
No Overflow, leakage, blockage, or damage
Yes
Proper slope, drain line ok, drainage acceptable, discharge okay
No
DOAS 2 - Condensate drain line broken.
Fans and Motors
Check OK Comments
Condition
Operational
Yes
No unusual odors, noise, or vibration
No
DOAS 1 - Whistling sound near MUNTERS label, possible air leakage (minor).
Central Plant
Check OK Comments
Heating Central Plant
Boiler operational
Yes
Misc. Comments
RAHU-1 - Weather-stripping broken on filter door.

WO # 177413
Work Order Number(s)
177413
Issues found durring this assessment have been assigned to the above work order(s).