School
Assessor
Hummy Khan
Date
Outdoor Temperature
39°F
Relative Humidity
43%
Outdoor Dew Point
19°F
Air Handling Unit (Assess representative sample of RTU/AHU, including Portables)
Check | OK | Comments |
---|---|---|
Tag Number | ||
Displayed
|
No
|
No tag numbers on rooftop units or exhaust fans.
|
Status | ||
Running
|
Yes
|
Check | OK | Comments |
---|---|---|
Outdoor Pollution | ||
Free from pollution sources w/i 25 ft. (e.g. dumpster, chimney, etc.)
|
Yes
|
|
Louvers and Access Doors | ||
Operating properly
|
Yes
|
|
Deflectors & Screens | ||
Present
|
Yes
|
|
No debris
|
Yes
|
|
Dampers | ||
Outside air damper: no obstructions
|
No
|
RTU located southwest side and towards the back & right hand side facing the building and bigger RTU on higher roof - Outside air dampers barely open. Smaller RTU on higher roof outside air dampers appear to be closed.
|
Return air damper: no obstructions
|
No
|
RTU (southeast side of building) - Return air dampers less open compared to other units.
|
Check | OK | Comments |
---|---|---|
Clean | ||
No excess dirt, not used for storage
|
No
|
Governair RTU (2nd closest unit to roof hatch) - Fan assembly very dirty. Governair RTU (located southwest side) box stored in mixing plenum.
|
Insulation | ||
Secure and Clean
|
Yes
|
|
P-Trap (if present) | ||
Charged with liquid
|
Yes
|
Check | OK | Comments |
---|---|---|
Filters | ||
Free of any bypassing
|
Yes
|
|
Correct size
|
Yes
|
|
Free from excessive loading, dampness or odor
|
Yes
|
|
Not collapsed/not fallen off
|
No
|
Governair RTU-5 (written by hand-first unit closest to roof hatch)- Filter end cover plate screws missing and cover plate can fall off from air pressure creating a bypass. Smaller unit on higher roof the end cover plate laying on floor.
|
Present (not missing)
|
Yes
|
|
Date and initials written
|
Yes
|
|
Heating Coils | ||
Clean, no noticeable leaks, or obstructions
|
Yes
|
|
Cooling Coils | ||
Clean, no noticeable leaks, or obstructions
|
Yes
|
|
Access: Free of any obstructions in area that may affect access
|
Yes
|
|
Condensation: No excess condensation problems
|
Yes
|
|
Blowoff: Free of water from coil blowoff
|
Yes
|
|
Condensate Pan and Drain Line | ||
No visible bacterial or fungal growth
|
Yes
|
|
Clean, no residue, no standing water
|
Yes
|
|
No Overflow, leakage, blockage, or damage
|
Yes
|
|
Proper slope, drain line ok, drainage acceptable, discharge okay
|
No
|
Bigger RTU on higher roof- Condensate drain improperly terminated.
|
Check | OK | Comments |
---|---|---|
Condition | ||
Operational
|
Yes
|
|
No unusual odors, noise, or vibration
|
Yes
|
Check | OK | Comments |
---|---|---|
Heating Central Plant | ||
Boiler operational
|
Yes
|
Check | OK | Comments |
---|---|---|
Thermostat | ||
Thermostat setting acceptable
|
No
|
Portable 35- Auxiliary heat on. Portable 184 and 210- Thermostat display screen message "Change air filter" alarm.
|
Thermostat cover
|
No
|
Portable 35 -t Thermostat front cover missing.
|
Fan Mode Correct
|
Yes
|
|
Space Temperature Acceptable
|
No
|
Portable 35- Motion sensor does not appear to be working and maintaining occupied set point temperature. Portable 184 and 210- do not appear to have motion sensors and maintaining occupied set point temperature.
|
Misc. Comments
Work Order: 176693.
Work Order Number(s)
176693
Issues found durring this assessment have been assigned to the above
work order(s).