Finding Type
Visible mold on surfaces due to elevated relative humidity/dew point
Remediation
Building Services investigated and addressed overcooling of mechanical equipment causing condensation on ventilation units and uninsulated pipes above the drop ceiling. The chilled water temperature was raised and portions of pipes insulated as necessary. Details listed in work order 163909.
Location
Room 120 and 171
Tracking Number
FXWFES2020001EEA
Assigned To
Building Services
Work Orders
#163909
(Complete)
Closed
Yes
Completion Date