School
Assessor
Christopher Madden
Date
Air Distribution and Terminal System (Assess 2-3 Locations per HVAC Zone)
Check | OK | Comments |
---|---|---|
Condition | ||
No odors, noise or vibration
|
No
|
Room 107 - Excessive noise coming from Fan Coil Unit. Belts need to be checked (WO #167414).
|
Clean, no obstructions
|
Yes
|
|
Free from signs of moisture/mold, insects or rodents?
|
Yes
|
|
No noticeable air leaks
|
Yes
|
Check | OK | Comments |
---|---|---|
Ceiling Tiles | ||
Tight seal on all tiles
|
Yes
|
|
No stained/damaged tiles indicating high RH or moisture problem
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
No odors or unusual sounds
|
Yes
|
|
Clean, no excess dirt or moisture
|
No
|
Cafeteria, Room 116, and 115 - Supply diffusers dirty (requires high dusting).
|
No obstruction to air flow
|
Yes
|
|
No purposely placed obstruction indicating occupant distress
|
Yes
|
|
Location | ||
No short circuiting between supply and return
|
Yes
|
|
Doors | ||
Doors not tight or difficult to close indicating large pressure differential
|
Yes
|
Building
Check | OK | Comments |
---|---|---|
Foundation | ||
No moisture penetration or signs of mold?
|
No
|
Portable 166 - Elevated moisture in drywall near the main entry door as determined with a moisture meter (WO #166651).
Portable 60 - Elevated moisture in drywall at front and back door. As a result, mold growth was observed on the backside of the wallpaper (one square foot) (See IEQ Concern CXMHMS2020000185 for additional details).
|
Doors and Windows | ||
Caulking and weather stripping in good condition
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
Room is free of dust and clutter
|
Yes
|
|
No stained or damage ceiling tiles
|
No
|
Back Stage Left (Down the Stairs) - Stained Ceiling Tile
|
No visible mold present (walls, cabinets, under sinks, behind posters)
|
No
|
Room 107 - Mold within the fume hood, due to lack of HVAC during COVID closure and the fume hood was closed. The impacted area was cleaned upon discovery. No further action is warranted.
|
Relative Humidity | ||
Not above 70%
|
No
|
Various rooms were above 70% humidity. Supply air temperatures were also elevated. The chiller was found to be in alarm. Building Services (HVAC) was contacted to respond (WO #166062). No mold growth was identified.
|
Check | OK | Comments |
---|---|---|
Condition | ||
Clean
|
Yes
|
|
No unusual noise or odor
|
Yes
|
|
No mold growth on insulation
|
Yes
|
|
Traps contain water
|
Yes
|
|
Chemical Storage | ||
Containers capped
|
Yes
|
|
No evidence of an active spill
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
No odors, or unusual noise or vibration
|
Yes
|