Indoor Environmental Quality General Assessment of Bryant Woods Elementary School: August 19th, 2020 (GXBWES2020000017)

Assessor
Jeffrey Klenk
Date

Air Distribution and Terminal System (Assess 2-3 Locations per HVAC Zone)

Ductwork (Supply and Return)
Check OK Comments
Condition
No odors, noise or vibration
Yes
Clean, no obstructions
Yes
Free from signs of moisture/mold, insects or rodents?
Yes
No noticeable air leaks
Yes
Plenum
Check OK Comments
Ceiling Tiles
Tight seal on all tiles
Yes
No stained/damaged tiles indicating high RH or moisture problem
Yes
Supply Diffusers, Return Grilles, Exhaust Grilles
Check OK Comments
Condition
No odors or unusual sounds
Yes
Clean, no excess dirt or moisture
No
The back side of the supply air diffsuer fins are dirty in rooms 116 and 130. Custodial staff is to clean.
No obstruction to air flow
Yes
No purposely placed obstruction indicating occupant distress
Yes
Location
No short circuiting between supply and return
Yes
Doors
Doors not tight or difficult to close indicating large pressure differential
No
Portable 204 - Both doors have daylight shining through. The ramp door has weather stripping peeling off. Work Order 164778.

Building

Envelope
Check OK Comments
Foundation
No moisture penetration or signs of mold?
No
Portable 118 - the drywall to the bottom left side of the ramp door indicated to be wet via a moisture meter calibrated to drywall. No mold was observed when opening a small inspection cut out from a previous inspection. Work Order 164780.
Doors and Windows
Caulking and weather stripping in good condition
Yes
Classrooms (Assess 2 to 3 per HVAC System Zone)
Check OK Comments
Condition
Room is free of dust and clutter
Yes
No stained or damage ceiling tiles
No
Water stained ceiling tiles were observed in 130 (2 tiles), portable 204 (2 tiles), server room of 156 (mold present), and hallway outside cafeteria doors towards the gym. Custodial staff is to submit a work order to Building Services if one is not already in progress.
No visible mold present (walls, cabinets, under sinks, behind posters)
Yes
Relative Humidity
Not above 70%
Yes
Mechanical/Boiler Rooms (Assess Each)
Check OK Comments
Condition
Clean
Yes
No unusual noise or odor
Yes
No mold growth on insulation
Yes
Traps contain water
Yes
Chemical Storage
Containers capped
Yes
No evidence of an active spill
Yes
Fan Coil Units/VAV Boxes
Check OK Comments
Condition
No odors, or unusual noise or vibration
No
Wall mounted HVAC unit in server room of the media workroom (156) was dirty. Work Order 164781.