Indoor Environmental Quality General Assessment of Ilchester Elementary School: July 28th, 2020 (GXXIES2020000001)

Assessor
Christopher Madden
Date

Air Distribution and Terminal System (Assess 2-3 Locations per HVAC Zone)

Ductwork (Supply and Return)
Check OK Comments
Condition
No odors, noise or vibration
Yes
Clean, no obstructions
Yes
Free from signs of moisture/mold, insects or rodents?
Yes
No noticeable air leaks
Yes
Plenum
Check OK Comments
Ceiling Tiles
Tight seal on all tiles
Yes
No stained/damaged tiles indicating high RH or moisture problem
Yes
Supply Diffusers, Return Grilles, Exhaust Grilles
Check OK Comments
Condition
No odors or unusual sounds
Yes
Clean, no excess dirt or moisture
Yes
No obstruction to air flow
Yes
No purposely placed obstruction indicating occupant distress
Yes
Location
No short circuiting between supply and return
Yes
Doors
Doors not tight or difficult to close indicating large pressure differential
Yes

Building

Envelope
Check OK Comments
Foundation
No moisture penetration or signs of mold?
Yes
Doors and Windows
Caulking and weather stripping in good condition
No
Room 130 - Condensation in window, possible break in seal (WO# 107570).
Classrooms (Assess 2 to 3 per HVAC System Zone)
Check OK Comments
Condition
Room is free of dust and clutter
No
Room 132 - Dead bug in light fixture. Room 251 - Multiple items hanging from ceiling.
No stained or damage ceiling tiles
No
Hallway (Across from Room 240, Outside of Bathrooms), Room 231 - Stained Ceiling Tile(s).
No visible mold present (walls, cabinets, under sinks, behind posters)
Yes
Relative Humidity
Not above 70%
No
Room 245 (78.6%), Room 251 (73.9%), and Room 248 (75.8%) - HVAC was operational within these areas. Supply temperatures appeared to be elevated. Building Services (HVAC) was contacted by phone. The Office of the Environment requested the HVAC units be turned off until the issue was resolved (WO #162547). No relative humidity mold growth was observed on surfaces.
Mechanical/Boiler Rooms (Assess Each)
Check OK Comments
Condition
Clean
Yes
No unusual noise or odor
Yes
No mold growth on insulation
Yes
Traps contain water
Yes
Chemical Storage
Containers capped
Yes
No evidence of an active spill
Yes
Fan Coil Units/VAV Boxes
Check OK Comments
Condition
No odors, or unusual noise or vibration
Yes