Assessor
John Farmer
Date
Outdoor Temperature
61°F
Relative Humidity
54%
Outdoor Dew Point
44°F
Air Handling Unit (Assess representative sample of RTU/AHU, including Portables)
Check | OK | Comments |
---|---|---|
Tag Number | ||
Displayed
|
No
|
DES CHAMPS: No tag number.
|
Status | ||
Running
|
Yes
|
Check | OK | Comments |
---|---|---|
Outdoor Pollution | ||
Free from pollution sources w/i 25 ft. (e.g. dumpster, chimney, etc.)
|
Yes
|
|
Louvers and Access Doors | ||
Operating properly
|
Yes
|
|
Deflectors & Screens | ||
Present
|
Yes
|
|
No debris
|
Yes
|
|
Dampers | ||
Outside air damper: no obstructions
|
No
|
ACU-2: Air dampeners appeared to be closed.
|
Return air damper: no obstructions
|
Yes
|
Check | OK | Comments |
---|---|---|
Clean | ||
No excess dirt, not used for storage
|
No
|
HV-1: Metal being stored in the unit.
OAAHU-4: Old filters and gaskets were observed in the unit.
|
Insulation | ||
Secure and Clean
|
Yes
|
|
P-Trap (if present) | ||
Charged with liquid
|
Yes
|
Check | OK | Comments |
---|---|---|
Filters | ||
Free of any bypassing
|
No
|
OOAHU-1, OOAHU-2, OOAHU-3, OOAHU-4 - Filter bypass observed due to filter damage/collapse.
|
Correct size
|
Yes
|
|
Free from excessive loading, dampness or odor
|
No
|
RAHU-1 (filters farthest from door), OOAHU-3, OOAHU-4 - Filters loaded.
|
Not collapsed/not fallen off
|
No
|
OAAHU-1: Filters were observed to be damaged.
OAAHU-2: Filters were observed to be damaged.
OAAHU-3: Pre-filters have collapsed.
OAAHU-4: Filters collapsed.
|
Present (not missing)
|
No
|
AHU-1, AHU-2, HV-1: Missing pre-filters.
|
Date and initials written
|
Yes
|
|
Heating Coils | ||
Clean, no noticeable leaks, or obstructions
|
Yes
|
|
Cooling Coils | ||
Clean, no noticeable leaks, or obstructions
|
No
|
OOAHU-1: Debris on coils.
OOAHU-4: Rust observed to be at bottom of coils.
|
Access: Free of any obstructions in area that may affect access
|
Yes
|
|
Condensation: No excess condensation problems
|
Yes
|
|
Blowoff: Free of water from coil blowoff
|
Yes
|
|
Condensate Pan and Drain Line | ||
No visible bacterial or fungal growth
|
Yes
|
|
Clean, no residue, no standing water
|
Yes
|
|
No Overflow, leakage, blockage, or damage
|
Yes
|
|
Proper slope, drain line ok, drainage acceptable, discharge okay
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
Operational
|
Yes
|
|
No unusual odors, noise, or vibration
|
Yes
|
Check | OK | Comments |
---|---|---|
Heating Central Plant | ||
Boiler operational
|
Yes
|
Work Order Number(s)
45567
Issues found durring this assessment have been assigned to the above
work order(s).
OOAHU-1: Door gaskets not sealing properly
OOAHU-3: Door gaskets not sealing properly