Assessor
Christopher Madden
Date
Outdoor Temperature
62°F
Relative Humidity
72%
Outdoor Dew Point
52°F
Air Handling Unit (Assess representative sample of RTU/AHU, including Portables)
Check | OK | Comments |
---|---|---|
Tag Number | ||
Displayed
|
Yes Work Order Closed by Building Maintenance
|
The exhaust fans do not have tag numbers.
On some units, the identification (marker or paint) has worn off. Consider permanent tags.
|
Status | ||
Running
|
Yes
|
Check | OK | Comments |
---|---|---|
Outdoor Pollution | ||
Free from pollution sources w/i 25 ft. (e.g. dumpster, chimney, etc.)
|
Yes
|
|
Louvers and Access Doors | ||
Operating properly
|
Yes
|
|
Deflectors & Screens | ||
Present
|
Yes
|
|
No debris
|
Yes
|
|
Dampers | ||
Outside air damper: no obstructions
|
Yes Work Order Closed by Building Maintenance
|
RTU-6 - Outside air dampers closed.
|
Return air damper: no obstructions
|
Yes
|
Check | OK | Comments |
---|---|---|
Clean | ||
No excess dirt, not used for storage
|
Yes
|
|
Insulation | ||
Secure and Clean
|
Yes
|
|
P-Trap (if present) | ||
Charged with liquid
|
Yes
|
Check | OK | Comments |
---|---|---|
Filters | ||
Free of any bypassing
|
Yes
|
|
Correct size
|
Yes
|
|
Free from excessive loading, dampness or odor
|
Yes Work Order Closed by Building Maintenance
|
RTU-1 and 2 - Moderate filter loading. Slated for replacement this month.
|
Not collapsed/not fallen off
|
Yes Work Order Closed by Building Maintenance
|
RTU-1 - One filter has fallen. Attempted to reset but it fell again. The clips need to be repaired or replaced.
|
Present (not missing)
|
Yes
|
|
Date and initials written
|
Yes
|
|
Heating Coils | ||
Clean, no noticeable leaks, or obstructions
|
Yes Work Order Closed by Building Maintenance
|
RTU-3 - Minor dust on coils.
|
Cooling Coils | ||
Clean, no noticeable leaks, or obstructions
|
Yes Work Order Closed by Building Maintenance
|
RTU-3 - Minor dust on coils.
|
Access: Free of any obstructions in area that may affect access
|
Yes
|
|
Condensation: No excess condensation problems
|
Yes
|
|
Blowoff: Free of water from coil blowoff
|
Yes
|
|
Condensate Pan and Drain Line | ||
No visible bacterial or fungal growth
|
Yes
|
|
Clean, no residue, no standing water
|
Yes
|
|
No Overflow, leakage, blockage, or damage
|
Yes
|
|
Proper slope, drain line ok, drainage acceptable, discharge okay
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
Operational
|
Yes
|
|
No unusual odors, noise, or vibration
|
Yes
|
Check | OK | Comments |
---|---|---|
Heating Central Plant | ||
Boiler operational
|
Yes
|
Check | OK | Comments |
---|---|---|
Thermostat | ||
Thermostat setting acceptable
|
Yes Work Order Closed by Building Maintenance
|
Portable 183 - The thermostat is set too low. It was not corrected while onsite because there is no lockbox. The thermostat should be corrected when re-installing the lockbox.
|
Thermostat cover
|
Yes Work Order Closed by Building Maintenance
|
Portable 216 - The front lock box cover has been removed from all of the rooms.
Portable 183 - The lockbox (to include the drywall anchors) has been removed from the wall.
|
Fan Mode Correct
|
Yes
|
|
Space Temperature Acceptable
|
Yes
|
Work Order Number(s)
26184
Issues found durring this assessment have been assigned to the above
work order(s).
RTU-7 - The dampers were open while the unit was off. When the unit came on, they did not appear to move.