Finding Type
Odors
Remediation
Building Maintenance was sent to the site and it was identified that Room 026 did not have an occupancy sensor, which was keeping the Variable Air Volume (VAV) boxes in the room from supplying air.
Building Maintenance (HVAC) temporarily bypassed the occupancy sensor input and the VAV boxes are now supplying air to the room. The HVAC contractor will be adding an occupancy sensor to the room which, when it is installed, will allow the VAV boxes to go to shutoff when there are no occupants in the room
Location
Room 26
Tracking Number
FXCRES202300265A
Assigned To
Building Services
Closed
Yes
Completion Date