Indoor Environmental Quality HVAC Assessment of Homewood Center: April 13th, 2023 (HXXXHC20230000CE)

Assessor
Jeffrey Klenk
Date
Outdoor Temperature
79°F
Relative Humidity
30%
Outdoor Dew Point
44°F

Air Handling Unit (Assess representative sample of RTU/AHU, including Portables)

Unit
Check OK Comments
Tag Number
Displayed
Yes
Status
Running
Yes
Outdoor Air Intake and Outdoor Air Dampers
Check OK Comments
Outdoor Pollution
Free from pollution sources w/i 25 ft. (e.g. dumpster, chimney, etc.)
Yes
Louvers and Access Doors
Operating properly
Yes
Deflectors & Screens
Present
Yes
No debris
Yes
Dampers
Outside air damper: no obstructions
Yes
Work Order Closed by Building Maintenance
Outdoor air dampers closed or in question as to minimum opening for RTUs 1, 3, 4, and 5.
Return air damper: no obstructions
Yes
Mixing Plenum
Check OK Comments
Clean
No excess dirt, not used for storage
Yes
Insulation
Secure and Clean
Yes
Work Order Closed by Building Maintenance
The sound liner on the air supply end in RTU 2 was detaching and would eventually fall on top of turning vanes.
P-Trap (if present)
Charged with liquid
Yes
Filters and Coils
Check OK Comments
Filters
Free of any bypassing
Yes
Correct size
Yes
Free from excessive loading, dampness or odor
Yes
Not collapsed/not fallen off
Yes
Present (not missing)
Yes
Work Order Closed by Building Maintenance
A pre-air filter was missing in RTU 1, however, the final box filter was present.
Date and initials written
Yes
Heating Coils
Clean, no noticeable leaks, or obstructions
Yes
Cooling Coils
Clean, no noticeable leaks, or obstructions
Yes
Access: Free of any obstructions in area that may affect access
Yes
Condensation: No excess condensation problems
Yes
Blowoff: Free of water from coil blowoff
Yes
Condensate Pan and Drain Line
No visible bacterial or fungal growth
Yes
Clean, no residue, no standing water
Yes
No Overflow, leakage, blockage, or damage
Yes
Work Order Closed by Building Maintenance
Exterior condensate drain pipe damage and/or disconnected for RTU-1 and RTU-5.
Proper slope, drain line ok, drainage acceptable, discharge okay
Yes
Fans and Motors
Check OK Comments
Condition
Operational
Yes
Work Order Closed by Building Maintenance
The supply fan belt on RTU-6 appears to have too much deflection. The return fan belt on RTU-3 appears to have too much deflection.
No unusual odors, noise, or vibration
Yes
Central Plant
Check OK Comments
Heating Central Plant
Boiler operational
Yes
Portable(s)
Check OK Comments
Thermostat
Thermostat setting acceptable
Yes
Thermostat cover
Yes
Fan Mode Correct
Yes
Space Temperature Acceptable
Yes
Misc. Comments
Assessor pieced back the condensate line for RTU-5.
Work Order Number(s)
279002, 279004, 279005, 279008, 279009
Issues found durring this assessment have been assigned to the above work order(s).