School
Assessor
Hummy Khan
Date
Outdoor Temperature
47°F
Relative Humidity
57%
Outdoor Dew Point
32°F
Air Handling Unit (Assess representative sample of RTU/AHU, including Portables)
Check | OK | Comments |
---|---|---|
Tag Number | ||
Displayed
|
Yes Work Order Closed by Building Maintenance
|
No tag numbers on two rooftop units.
No tag numbers on any exhaust fans, repeat finding.
|
Status | ||
Running
|
Yes
|
Check | OK | Comments |
---|---|---|
Outdoor Pollution | ||
Free from pollution sources w/i 25 ft. (e.g. dumpster, chimney, etc.)
|
Yes
|
|
Louvers and Access Doors | ||
Operating properly
|
Yes
|
|
Deflectors & Screens | ||
Present
|
Yes
|
|
No debris
|
Yes
|
|
Dampers | ||
Outside air damper: no obstructions
|
Yes
|
|
Return air damper: no obstructions
|
Yes Work Order Closed by Building Maintenance
|
AHU-7 - Inlet vanes closed.
|
Check | OK | Comments |
---|---|---|
Clean | ||
No excess dirt, not used for storage
|
Yes
|
|
Insulation | ||
Secure and Clean
|
Yes
|
|
P-Trap (if present) | ||
Charged with liquid
|
Yes
|
Check | OK | Comments |
---|---|---|
Filters | ||
Free of any bypassing
|
Yes Work Order Closed by Building Maintenance
|
AHU-4 - Air bypass around filters.
|
Correct size
|
Yes Work Order Closed by Building Maintenance
|
AHU-4- Incorrect size filters. Install correct size filters or blank plates to prevent air bypass.
|
Free from excessive loading, dampness or odor
|
Yes Work Order Closed by Building Maintenance
|
AAON (only one unit) - Filters dirty.
|
Not collapsed/not fallen off
|
Yes
|
|
Present (not missing)
|
Yes
|
|
Date and initials written
|
Yes Work Order Closed by Building Maintenance
|
AHU (no tag number) - No dates on final filters.
AAON (only one unit)- No dates on filters. On all other units, the filters had been replaced on March 17, 2023.
|
Heating Coils | ||
Clean, no noticeable leaks, or obstructions
|
Yes
|
|
Cooling Coils | ||
Clean, no noticeable leaks, or obstructions
|
Yes
|
|
Access: Free of any obstructions in area that may affect access
|
Yes
|
|
Condensation: No excess condensation problems
|
Yes
|
|
Blowoff: Free of water from coil blowoff
|
Yes
|
|
Condensate Pan and Drain Line | ||
No visible bacterial or fungal growth
|
Yes
|
|
Clean, no residue, no standing water
|
Yes
|
|
No Overflow, leakage, blockage, or damage
|
Yes
|
|
Proper slope, drain line ok, drainage acceptable, discharge okay
|
Yes Work Order Closed by Building Maintenance
|
Except for two units, condensate drain improperly terminated on all units.
AHU (no tag number) - Broken condensate drain line.
|
Check | OK | Comments |
---|---|---|
Condition | ||
Operational
|
Yes
|
|
No unusual odors, noise, or vibration
|
Yes Work Order Closed by Building Maintenance
|
Three exhaust fans noisy/vibrating. One near AHU-3, second located between AHU-1 and AHU-2 and third between AHU-2 and AHU-3.
|
Check | OK | Comments |
---|---|---|
Chilled Water Central Plant | ||
Chiller operational
|
Yes
|
Turned off due to heating season.
|
Heating Central Plant | ||
Boiler operational
|
Yes
|
Check | OK | Comments |
---|---|---|
Thermostat | ||
Thermostat setting acceptable
|
Yes Work Order Closed by Building Maintenance
|
Portable# 8 - Cooling set point 76 degrees, HCPSS standard 74 deg. While on site changed it to 74 deg.
Portable#220 -"Change air filter" alarm on thermostat screen display.
|
Thermostat cover
|
Yes
|
|
Fan Mode Correct
|
Yes
|
|
Space Temperature Acceptable
|
Yes
|
Work Order Number(s)
276405
Issues found durring this assessment have been assigned to the above
work order(s).