Indoor Environmental Quality HVAC Assessment of Ilchester Elementary School: January 27th, 2023 (HXXIES20230000B9)

Assessor
Hummy Khan
Date
Outdoor Temperature
39°F
Relative Humidity
30%
Outdoor Dew Point
13°F

Air Handling Unit (Assess representative sample of RTU/AHU, including Portables)

Unit
Check OK Comments
Tag Number
Displayed
Yes
Work Order Closed by Building Maintenance
No tag numbers on any rooftop units (RTUs) and exhaust fans (EFs), repeat findings. On one RTU, the number is scratched in but not sure if that is the tag number.
Status
Running
Yes
Outdoor Air Intake and Outdoor Air Dampers
Check OK Comments
Outdoor Pollution
Free from pollution sources w/i 25 ft. (e.g. dumpster, chimney, etc.)
Yes
Louvers and Access Doors
Operating properly
Yes
Deflectors & Screens
Present
Yes
No debris
Yes
Dampers
Outside air damper: no obstructions
Yes
Return air damper: no obstructions
Yes
Mixing Plenum
Check OK Comments
Clean
No excess dirt, not used for storage
Yes
Insulation
Secure and Clean
Yes
P-Trap (if present)
Charged with liquid
Yes
Filters and Coils
Check OK Comments
Filters
Free of any bypassing
Yes
Work Order Closed by Building Maintenance
RTU-2 and another RTU (no tag number-located towards the back of building) - Pre-filter is not the correct size causing air bypass.
Correct size
Yes
Work Order Closed by Building Maintenance
RTU-2 and another RTU (no tag number-located towards the back of building) - Pre-filter is not the correct size causing air bypass.
Free from excessive loading, dampness or odor
Yes
Not collapsed/not fallen off
Yes
Present (not missing)
Yes
Date and initials written
Yes
Heating Coils
Clean, no noticeable leaks, or obstructions
Yes
Cooling Coils
Clean, no noticeable leaks, or obstructions
Yes
Access: Free of any obstructions in area that may affect access
Yes
Condensation: No excess condensation problems
Yes
Blowoff: Free of water from coil blowoff
Yes
Condensate Pan and Drain Line
No visible bacterial or fungal growth
Yes
Clean, no residue, no standing water
Yes
No Overflow, leakage, blockage, or damage
Yes
Proper slope, drain line ok, drainage acceptable, discharge okay
Yes
Fans and Motors
Check OK Comments
Condition
Operational
Yes
No unusual odors, noise, or vibration
Yes
Central Plant
Check OK Comments
Heating Central Plant
Boiler operational
Yes
Portable(s)
Check OK Comments
Thermostat
Thermostat setting acceptable
Yes
Work Order Closed by Building Maintenance
Portable 184-"Change air filter" and "Cancel Alarm" messages on the thermostat display screen.
Thermostat cover
Yes
Work Order Closed by Building Maintenance
Portable 35- Thermostat cover missing.
Fan Mode Correct
Yes
Space Temperature Acceptable
Yes
Work Order Number(s)
270448
Issues found durring this assessment have been assigned to the above work order(s).