Finding: River Hill High School: Classroom # 256 (FXRHHS2023002500)

Finding Type
Miscellaneous finding
Comments
Space temperature 72.4 deg. Air conditioning running earlier in the day in most of the areas of the building while they are unoccupied during the summer vacation and overcooling the spaces below the HCPSS Guidelines for Energy Conservation setting of 76 deg. for cooling.

Plus, per the Memorandum, in summer, air conditioning is supposed to run only from 4 pm to 6 pm on weekdays if there's no summer school, summer camp, and/or if custodial requested. Building Maintenance HVAC Department is to review the HVAC operations schedule for the school and temperature set point.
Location
Classroom # 256
Tracking Number
FXRHHS2023002500
Assigned To
Building Services
Work Orders
#293949
(Complete)
Closed
Yes
Completion Date