Finding: Pointers Run Elementary School: Portable Villa (FXPRES20230023C7)

Finding Type
Miscellaneous finding
Comments
Air conditioning running in the entire villa during the day and most of the rooms are being overcooled during the summer vacation while no one is in there. For example room #8, 71.5 deg. Per the HVAC department Summer Operations Schedule, portable thermostat cooling set point should be set at 82 degrees F during the summer. All rooms thermostats need to be checked for proper temperature setting and set at HCPSS standard temperature setting for the summer.
Location
Portable Villa
Tracking Number
FXPRES20230023C7
Assigned To
Building Services
Work Orders
#290289
(Complete)
Closed
Yes
Completion Date