Finding: Oakland Mills High School: Room # 701 and the entire zone (FXOMHS202300240F)

Finding Type
Miscellaneous finding
Comments
Air conditioning running earlier in the day in the entire section and maintaining 69.7 deg. and being overcooled while it is unoccupied during summer vacation. In summer, air conditioning is supposed to run only from 4 pm to 6 pm on weekdays and maintain 76 deg. if there's no summer school, summer camp, and/or if custodial requested. Building Maintenance is to review the HVAC operations schedule for the school and the temperature set point.
Location
Room # 701 and the entire zone
Tracking Number
FXOMHS202300240F
Assigned To
Building Services
Work Orders
#290594
(Complete)
Closed
Yes
Completion Date