Finding: Mount View Middle School: Student Service Office (FXMVMS20220020EE)

Finding Type
Miscellaneous finding
Remediation

Building Maintenance (HVAC) collected various static pressure measurements associated with the DOAS Unit (following the balometer readings) and identified inconsistencies when compared to the original balancing report. Building Maintenance (HVAC) utilized a balancing contractor to further investigate the low air flows. A loose bypass damper was identified and corrected (December 12, 2022). Follow-up static pressure readings were acceptable following the repair.

Location
Student Service Office
Tracking Number
FXMVMS20220020EE
Assigned To
Environmental Services
Closed
Yes
Completion Date